Modulation - outdoor reset - bacnet variable list – LAARS M4-LHS - Installation Manual User Manual

Page 45

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

45

M

OD

u

La

Ti

ON

- Ou

TDOO

r

rESET

- B

a

C

NET

V

aria

BLE

L

iST

Hybrid

Object ID

Object

Type

Object V

alue

Object Name

Units

Minimum

M

ax

im

um

Definition

Model

Device Object

Read Only

MODEL

Serial Number

Device Object

Read Only

SNUMBER

Version

Device Object

Read Only

VERSION

Operation Mode

100

MUL

TIST

ATE-V

ALUE

Read Only

OPMODE

1

3

1= Hybrid, 2 = Modulation Setpoint, 3 = Modulation Reset

Outdoor

Temperature

200

ANALOG-V

ALUE

Read Only

ODTEMP

Degree F

32000=OPEN,3201=SHOR

T

System

Temperature

300

ANALOG-V

ALUE

Read Only

SYSSEN

Degree F

32000=OPEN,3201=SHOR

T

Control Status

400

MUL

TIST

ATE-V

ALUE

Read Only

CST

AT

1

15

1=SHUTDOWN,2=NO

TST

AT

CALL,3=PROVE F

AILURE,4=

PURGE DLEA

Y,5=W

AITING FOR PROVE,6=SENSOR F

AUL

T,7=

LAG DELA

Y, 8=LAST

ST

AGE HOLD,9=DHW CALL,10 = SYSTEM

RUNON,1

1=SUMMER,12=OUTDOOR CUT

OFF

,13=BOOST

MODE,14=SETBACK MODE,15 = NORMAL

OPERA

TION

Season

500

MUL

TIST

ATE-V

ALUE

Read/W

rite

SEA

1

2

1= Winter

, 2= Summer

Reset Ratio

600

MUL

TIST

ATE-V

ALUE

Read/W

rite

RR

1

11

1 =1.00 OD = 4.00 Sys,2 =1.00 OD = 3.00 Sys,3 =1.00 OD = 2.00 Sys, 4 =1.00 OD = 1.50 Sys,5 =1.00 OD = 1.25 Sys,6 =1.00 OD = 1.00 Sys,,7 =1.25 OD = 1.00 Sys,8 =1.50 OD = 1.00 Sys,9 =2.00 OD = 1.00 Sys,10 =3.00 OD = 1.00 Sys,1

1 = 4.00 OD = 1.00 Sys

Of

fset

700

ANALOG-V

ALUE

Read/W

rite

OFF

Degree F

-50

50

Integer V

alues Only (-1,0,1,2…)

Outdoor Cutof

f

800

ANALOG-V

ALUE

Read/W

rite

CO

Degree F

19

101

Integer V

alues Only (19,20,21…)

Min W

ater

Temp

900

ANALOG-V

ALUE

Read/W

rite

MINW

Degree F

50

180

Integer V

alues Only (50,51,52…)

Max W

ater

Temp

1000

ANALOG-V

ALUE

Read/W

rite

MAXW

Degree F

70

220

Integer V

alues Only (70,71,72…)

Setback

1100

ANALOG-V

ALUE

Read/W

rite

SB

Degree F

0

75

Integer V

alues Only (0,1,2…)

Purge Delay

1200

ANALOG-V

ALUE

Read/W

rite

PDL

Y

Minutes

.1

10

.1 thru .9 after Integer V

alues Only (1,2…)

System Runon

1300

ANALOG-V

ALUE

Read/W

rite

RUNON

Minutes

0

360

Integer V

alues Only (0,1,2…)

Rotation

Time

1400

ANALOG-V

ALUE

Read/W

rite

R

TTIME

Hours

1

1440

Hours since last rotation Integer V

alues Only (1,2,3…)

Standby

Time

1500

ANALOG-V

ALUE

Read/W

rite

STBYDL

Y

Minutes

1

60

Integer V

alues Only (1,2,3…)

Last Stage Hold

1600

ANALOG-V

ALUE

Read/W

rite

LSTHOLD

Degree F

0

30

Integer V

alues Only (0,1,2…)

Gain

1700

MUL

TIST

ATE-V

ALUE

Read/W

rite

GAIN

1

10

Lag Delay

1800

ANALOG-V

ALUE

Read/W

rite

LAGDL

Y

Minutes

0

60

Integer V

alues Only (0,1,2…)

Soft of

f

1900

ANALOG-V

ALUE

Read/W

rite

SOFF

Seconds

0

60

Integer V

alues Only (0,1,2…)

Set

Time

2000

ANALOG-V

ALUE

Read/W

rite

PTIME

Minutes

1

1440

Time since midnight Integer V

alues Only (1,2,3…)

Day Schedule

2100

ANALOG-V

ALUE

Read/W

rite

DSCHED

Minutes

1

1440

Time since midnight Integer V

alues Only (1,2,3…)

Night Schedule

2200

ANALOG-V

ALUE

Read/W

rite

NSCHED

Minutes

1

1440

Time since midnight Integer V

alues Only (1,2,3…)

System Relay

2300

BINAR

Y-V

ALUE

Read Only

SYSRL

Y

False

True

True = Energized, False = De-Engergized

Output Relays

2400 - Max Stages

BINAR

Y-V

ALUE

Read Only

R

Y0 - R

Y Max

Stages

False

True

True = Energized, False = De-Engergized