Boiler status, Display modulating boiler status, Display messages – LAARS M4-LHS - Installation Manual User Manual

Page 38: Boiler stage menu

Advertising
background image

HT# 059295-00

A

38

M4-LHS installation and Operation Manual

BOiLEr STaTuS

The M4-LHS boiler status gives immediate access to each boiler stages or modulation.

• ---

Boiler is off due to no call for heat.

• <<A>>

A is the lead boiler in the lead Hybrid group. See "Lead Stages" on page 32.

• <C>

C is the lead boiler in the lag Hybrid group or the lead boiler in Modulating Boiler Type. See "Lead Stages" on page 32.

• C/E

Extension panel is NOT communicating back to the M4-LHS. See "Connecting to the Extensions and 4-20mA EMS

Interface" on page 15.

• mON

All boiler stages are set to ON.

• mOFF

All boiler stages are set to OFF.

Display Modulating Boiler Status

• 97%

Boiler is modulating at the indicated percentage.

• m95%

Boiler Stage Mode is set to Manual Modulation to the specified percent. See "Mode" on page 39.

• h50%

Boiler is in post purge for 30 seconds.

DiSPLaY MESSagES

The M4-LHS display layout reserved the second line for message indications. The following is a list of the most common Message

Display Line information:

• Boost To 170˚F

The Boost has started 30 minutes before the Day Schedule setting and the Boost temperature is 170˚F.

See "Boost Mode" on page 25.

• DHW Call (180˚F)

There is an indirect DHW call. The M4-LHS will raise the system Set Point to the indicated temperature.

DHW increases calculated temperature to the DHW Set Point. See "Indirect Domestic Hot Water Set

Point" on page 24.

• Holding Until 150˚F

The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when system

temperature reaches 150˚F. See "Last Stage Hold" on page 32.

• Interface Module Error There is no communication to the BACnet Module Interface while the BACnet Mode is set to Enable.

See "BACnet Mode" on page 26.

• Lag Delay: 123

The lead boiler is at 100% and the remaining purge time to start the lag boiler in seconds is 123. See "Lag

Delay" on page 33.

• Outdoor Cutoff

The outdoor temperature is above the Outdoor Cutoff setting. No boilers will be active for heating. See

"Outdoor Cutoff Temperature" on page 30.

• Prove Failure

After boilers have run for some time, Prove signal has ended. All boilers set to Auto or Standby will

de-energize. However, the System relay will remain energized. See "Prove/Indirect Domestic Hot Water

(DHW) Priority" on page 24 and "Wiring the Prove" on page 13.

• Purge Delay: 23

A boiler is in purge cycle and the remaining purge time in seconds is 23. See "Purge Delay" on page 31.

• Setback to: 130˚F

The Night Schedule or Setback input is active. Current Setback temperature is 130˚F. See "Setback"

on page 31. See "Day - Night Schedule" on page 36.

• Shutdown Active

The Shutdown Terminals are Shorted. No boilers will be active. See "Shutdown/Tstat/Setback Mode" on

page 24. Also See "Wiring the Shutdown, Tstat, or Setback" on page 12.

• Summer

The control is set to Summer. No heat is active. See "Season" on page 27.

• Switch in: 00:30

The switch from one group to the other will take place after 30 minutes. See "Switch Delay" on page 21.

• System Run-On: 46

The System relay is ON for the System Run-On Delay. This example shows that it will remain in System

Run-On for an additional 46 seconds before turning off. See "System Run-On" on page 31.

• Tstat Call

The Tstat Terminals are Shorted. Boilers will be active. See "Shutdown/Tstat/Setback Mode" on page 24.

• Waiting for Prove

The System relay is ON and the prove terminals are open before the lead boiler relay can energize. See

"Prove/Indirect Domestic Hot Water (DHW) Priority" on page 24.

BOiLEr STagE MENu

Advertising