Hybrid modulating boiler settings, Modulating output type, Modulating mode – LAARS M4-LHS - Installation Manual User Manual

Page 22: Hybrid staging boiler settings, Staging output type, Staging mode, Warning

Advertising
background image

HT# 059295-00

A

22

M4-LHS installation and Operation Manual

HYBriD MODuLaTiNg BOiLEr SETTiNgS

Modulating Output Type

4-20mA, 0-10V, 1-10V (Custom) Outputs

Default: 1-10v Custom

Button: MENU/<System Startup>/..../Condensing Boiler Number/Output A Type

• If either of the Condensing or Non-Condensing Boiler groups was set to Modulating as the

Boiler Type, the M4-LHS will offer the capability of controlling a variety of modulating

signals. Each boiler can be configured to have a different modulating signal.

• The modulating output for each boiler can be configured to 4-20mA operation (Current) or

any of the voltage options. Check the boiler to determine its signal requirements.

• When using the Extension, connect it to the M4-LHS prior to configuring the Output Type.

Otherwise, the M4-LHS might not recognize the Extension stages.

Modulating Mode

Normal, Parallel

Default: Normal

Button: MENU/<System Startup>/..../Output A Type/Condensing Modulating Mode

• Some modulating boilers perform better at higher modulation. For these units, it is

advantageous to run one unit at high modulation than several units at lower modulation. If

the units used are of this type, select Normal. This is the recommended setting for boilers

with low turndown ratios.

• Most condensing boilers run more efficiently at lower modulation. If it is more energy

efficient to run several units at lower modulation than one at high. In this case select

Parallel. This is typically used on condensing boilers or boilers with high turndown ratios.

• For best Parallel performance, set the Modulation Start % to be equivalent to the lowest

firing rate of the boiler multiplied by 2. That is, if the lowest firing of the boiler was 20%,

set your Modulation Start% to 40%. See "Modulation Start %" on page 40.

Set the Lag Delay to 0 for better parallel performance. See "Lag Delay" on page 33.

CONDENSING

-- OUTPUT A TYPE --

4-20mA

0-10volt

0-5volt

2-10volt

1-5volt

BACK ▲ ▼ SAVE

WarNiNg

Make sure that boiler modulation

wiring matches the signal selected.

Warranty will not cover failed

components caused by improper

wiring. See "Wiring the Boilers" on

page 14.

CONDENSING

- MODULATING MODE -

Normal

Parallel

BACK ▲ ▼ SAVE

NON-CONDENSING

- MODULATING MODE -

Normal

Parallel

BACK ▲ ▼ SAVE

HYBriD STagiNg BOiLEr SETTiNgS

Staging Output Type

On/Off, 2-Stage, 3-Stage, 4-Stage Outputs

Default: On/Off

Button: MENU/<System Startup>/..../Non-Condensing Output Type

• The M4-LHS can sequence multi-stage boiler starting with a single On/Off and up to a

4-stages. Just select the number of stages per boiler from this menu option.

• For each boiler stage a single output relay will be used. That is a 2-stage boiler will use two

of the control stages.

• The number selected applies to all sequencing boilers within that group whether it is

Condensing or Non-Condensing.

• The maximum number of stages the control can operate is 4. But with the addition of up to

two extensions, it can handle up to a total of 16 stages.

NON-CONDENSING

-- OUTPUT TYPE --

On/Off

2-Stage

3-Stage

4-Stage

BACK ▲ ▼ SAVE

Staging Mode

Lo/Hi/Lo/Hi, Lo/Lo/Hi/Hi

Default: Lo/Hi/Lo/Hi

Button: MENU/<System Startup>/..../Non-Condensing Output Type/Non-Cond Staging Mode

• During low load conditions, some boilers run more efficient when the lower stages are

energized alone than with the higher stages. For these types of boilers select Lo/Lo/Hi/Hi.

Then, the M4-LHS will sequence the lower stages of all boilers set to Auto before

sequencing the higher stages.

• For the rest of the boiler types, the Lo/Hi/Lo/Hi should allow the staging of the lower stage

of the lead boiler followed by the higher stage of the same boiler. Then when more stages

are needed, it will fire the lower stage of the lag boiler followed by the higher stages

NON-CONDENSING

- STAGING MODE -

LO/HI/LO/HI

LO/LO/HI/HI

BACK ▲ ▼ SAVE

Advertising