Startup settings, Program change switch setting, Startup sequence – LAARS M4-LHS - Installation Manual User Manual

Page 19: Boiler type, Sensor type, Ems input mode, M4-lhs, A b c d, Hybrid control startup sequence

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

19

STarTuP SETTiNgS

Program Change Switch Setting

To be able to change the M4-LHS settings the Program/Run Switch must be set to Program.

The switch is located under the Enclosure Wiring Cover for security.

SYSTEM

A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

/TSTAT

M4-LHS

HYBRID CONTROL

Startup Sequence

Button: MENU/<System Startup>

• When powered, the M4-LHS performs a self diagnostics-test.

• On the first power up, the System Startup screen will appear after the initialization is

complete. If it doesn’t, the M4-LHS has already been configured.

• The System Startup menu sets the main parameters that relate to the heating application.

These settings must be set by the installer.

-------- SETTINGS ----

Season

Winter

System Target 140

o

F

<System Settings>

<Maintenance>

<Histories>

<System Startup>

BACK ▲ ▼ SELECT

Boiler Type

Modulation, Hybrid

Default: Modulation

Button: MENU/<System Startup>/..../Boiler Type

• The same Laars control can operate modulating boilers or a combination of both types.

• The Modulation option will operate a variety of modulating boiler signals.

• The Hybrid option will sequence two groups of boilers, condensing and non-condensing.

Each group could be of a different boiler type (Modulation or Staging). See "Hybrid Logic

Overview" on page 3. Each Multi-Stage boiler will use a single output relay for each stage.

• If BACnet is to be used, each of the Boiler Type modes will have a different set of BACnet

variables. See "Hybrid - Outdoor Reset - BACnet Variable list" on page 44.

--- BOILER TYPE ---

Modulation

Hybrid

BACK ▲ ▼ SAVE

Sensor Type

Reset °F, Reset °C, Set Point °F, Set Point °C, 4-20mA EMS

Default: Reset °F

(Set Point Options are Not Available with Hybrid Boiler Type)

Button: MENU/<System Startup>/..../Sensor Type

• If Reset °F is selected, all temperatures and settings will be displayed in degrees Fahrenheit

and the control will use Reset Ratios to adjust the system set point.

• If Reset °C is selected, all temperatures and settings will be displayed in degrees Celsius and

the control will use Reset Ratios to adjust the system set point.

• If Set Point °F is selected, all temperatures and settings will be displayed in degrees

Fahrenheit and the control will have an adjustable system set point.

• If Set Point °F is selected, all temperatures and settings will be displayed in degrees Celsius

and the control will have an adjustable system set point.

• The 4-20mA EMS option is only available to the Hybrid Boiler Type option. To use

4-20mA EMS with Modulating Boiler Type, select one of the Set Point options and the EMS

Input Mode menu will follow to offer the 4-20mA EMS option.

• The use of the 4-20mA EMS option requires the purchase of the 4-20mA EMS Interface. It

gives the M4-LHS the capability of accepting a remote 4-20mA signal from a BMS or EMS

system as the target set point.

• If BACnet is to be used, each of the Sensor Type modes will have a different set of BACnet

variables. See "Hybrid - Outdoor Reset - BACnet Variable list" on page 44.

Modulating Options

-- SENSOR TYPE --

Reset

o

F

Reset

o

C

Set Point

o

F

Set Point

o

C

BACK ▲ ▼ SAVE

Hybrid Options

--- SENSOR TYPE ---

Reset

o

F

Reset

o

C

4-20mA EMS

BACK ▲ ▼ SAVE

EMS input Mode

Disable, Enable

Default: Disable

(Available after Set Point with Modulation Boiler Types)

Button: MENU/<System Startup>/..../Boiler Type/Sensor Type / EMS Input Mode

• It allows the M4-LHS to utilize the 4-20mA EMS Interface to accept a remote 4-20mA

signal from a BMS or EMS system as the target set point.

- EMS INPUT MODE -

Disable

Enable

BACK ▲ ▼ SAVE