Offset, Outdoor cutoff temperature, Minimum water temp – LAARS M4-LHS - Installation Manual User Manual

Page 30: Maximum water temp, Custom reset ratio, Target offset

Advertising
background image

HT# 059295-00

A

30

M4-LHS installation and Operation Manual

Offset

Adjustable from 50Fº/28Cº to -50Fº/-28Cº

Default: 0Fº/0Cº

Button: MENU/System Target/Offset

• The Offset adjust the starting points of the Reset Ratio curve. This means that, regardless

of the Outdoor Temperature (OD) or the Reset Ratio that has been selected, when the

Offset setting is changed, that change is directly added to or subtracted from the calculated

temperature. For example, if the Set Point was 130°F and the Offset was changed from 0F°

to 10F° (an increase of 10F°), then the Set Point temperature would increase to 140°F.

• The Offset setting does not change the ratio selection. What the Offset does is add or

subtract a constant temperature value. See "Outdoor Reset Concept" on page 5.

------- OFFSET ------

+0

o

F

[ ]

BACK ▲ ▼ SAVE

• If required: Adjust the Water Offset in mild weather. If the ambient building

temperatures are too warm in mild weather, decrease the offset. If the ambient building

temperatures are too cold in mild weather, increase the Water Offset.

• The rule of thumb for baseboard radiation is to change the offset 4°F for every 1°F you wish

to change the building temperature. In radiant heat applications, change the offset 1F° or

2F° for every 1F° you wish to change the building temperature.

Outdoor Cutoff Temperature

Adjustable: Off, from 20ºF / 70ºC - 100ºF / 38ºC, On

Default: 65ºF/ 18ºC

Button: MENU/System Target/Offset/Outdoor Cutoff

• The control will turn heating off if the outside temperature rises above the Outdoor Cutoff.

This setting shall not affect any indirect DHW requirement.

• The Outdoor Cutoff screen will automatically appear after setting the Offset.

• When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the

M4-LHS will operate the boilers to hold the calculated temperature.

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater

Temperature (in °F)

Custom Reset Ratio

Point1: System=120°F

Oudoor=60°F

Point2: System=170°F

Oudoor=0°F

Point1

Point2

Customized Reset Ratio

Max Target

Min Target

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater

Temperature (in °F)

Target Offset

Offset=10°F

Reset Ratio=1.5 : 1.0

Reset Ratio

Max Target

Min Target

Reset Ratio + 10F Offset

Min Target=120°F

Max Target=170°F

• When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the

M4-LHS will turn all boilers off. The System relay will remain energized for the Run-On

delay then de-energize.

• The Outdoor Cutoff can be set from 20°F to 100°F. In addition, it can be set to ON or OFF.

In the ON position, the System Relay will run regardless of the Outdoor Temperature (OD)

and the burner stages will be active to hold the calculated water temperature. (Note: The

lowest water temperature the M4-LHS will circulate is 70°F. If the Outdoor Cutoff is turned

ON and the Season is set to Winter, the M4-LHS will circulate at least 70°F water even in

the hottest of weather.) In the OFF position, the system pump will always be off and all

burner stages will be off.

- OUTDOOR CUTOFF -

65

o

F

[

]

BACK ▲ ▼ SAVE

Minimum Water Temp

Adjustable from 50ºF/10ºC to 180ºF/82ºC

Hybrid Default: 70ºF/ 21ºC

Modulation Default: 120ºF/ 49ºC

Button: MENU/System Target/Offset/Outdoor Cutoff/Minimum Water Temp

• The Minimum Water Temperature must be set to the boiler manufacturer’s specification.

The M4-LHS will calculate the Set Point based on the Outdoor Temperature (OD), the Reset

Ratio, and the Offset value. The M4-LHS will control all boilers to hold either the Set Point

temperature, or the Minimum Water Temperature, whichever is higher.

• The Minimum Water Temperature must be at least 20°F lower than the Maximum

Temperature (See next setting).

MINIMUM WATER TEMP

70

o

F

[ ]

BACK ▲ ▼ SAVE

Maximum Water Temp

Adjustable 70ºF/21ºC - 220ºF/104ºC

Default: 200ºF/93ºC

Button: MENU/System Target/Offset/..../Maximum Water Temperature

• This is the highest temperature heating water the M4-LHS will circulate through the heating

system.

• When using a radiation system, it should be set according to the tubing or floor

manufacturer’s specification.

• The Maximum Temperature must be at least 20°F higher than the Minimum Temperature

(See previous setting).

MAXIMUM WATER TEMP

200

o

F

[

]

BACK ▲ ▼ SAVE