HT# 059295-00

A

M4-LHS installation and Operation Manual

15

Connecting to the Extensions and 4-20ma EMS interface

aLErT

To set the Extension to a specific letter, remove the wiring cover and switch the Ext A/Ext B to the

desired letter. DO NOT set both extensions to the same letter to avoid errors.

SYSTEM

A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

/TSTAT

M4-LHS

HYBRID CONTROL

• The M4-LHS is equipped with a RJ45 socket and a RJ45 to RJ11 Adaptor to connect to extension panels and X-SIG 4-20mA EMS

Interfaces. The Extension is equipped with two RJ11 sockets. It comes packaged with a RJ11 cable to connect to M4-LHS and an

additional Extension. Use the RJ45 to RJ11 Adaptor on the M4-LHS.

• The order in which the control, the extensions, and the interface are wired is not observed.

• Set each Extension to a different letter (EXT-A or EXT-B). The M4-LHS assigns the stage letters based on the extension letter

selected.

• Extension-A operates stages (E - J) and all the LEDs are Green. However, Extension-B operates stages (K - P) and all the LEDs

are Red. .

• Configure the Modulating and Sequencing Output Types after connecting the Extension panels to be able to configure their outputs.

See "Boiler Type" on page 19

• Use the 6-wire RJ11 cable supplied with the extension for proper operation.

SYSTEM

A
B
C
D

Full Modulation Sequencing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CLASS 1 WIRE ONLY.

PROVE

/DHW

SHUTDOWN

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

SYSTEM

A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

F
H
J
Power

CAUTION:

Risk of Electric Shock.

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PWR

L N
1 2

E

3 4

F

5 6

G

7 8

H

9 10

I

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

E
G

I

Comm

Ext B

K
M
O

L
N
P

17

16

VLT

mA

CUR / VLT

20

19

16

VLT

mA

GND

CUR / VLT

23

22

19

VLT

mA

GND

CUR / VLT

26

25

22

VLT

mA

GND

CUR / VLT

J

13114

K

M

O

L

N

P

E

F

G

H

K

M

L

N

15

GND

18

GND

21

GND

24

GND

29

28

VLT

mA

CUR / VLT

32

31

16

VLT

mA

GND

CUR / VLT

27

GND

30

GND

I

J

O

P

M4-Extension A

M4-Ext

FULL MODULATION SEQUENCING EXTENSION

F
H
J
Power

CAUTION:

Risk of Electric Shock.

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PWR

L N
1 2

E

3 4

F

5 6

G

7 8

H

9 10

I

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

E
G

I

Comm

Ext B

K
M
O

L
N
P

17

16

VLT

mA

CUR / VLT

20

19

16

VLT

mA

GND

CUR / VLT

23

22

19

VLT

mA

GND

CUR / VLT

26

25

22

VLT

mA

GND

CUR / VLT

J

13 14

K

M

O

L

N

P

E

F

G

H

K

M

L

N

15

GND

18

GND

21

GND

24

GND

29

28

VLT

mA

CUR / VLT

32

31

16

VLT

mA

GND

CUR / VLT

27

GND

30

GND

I

J

O

P

M4-Extension B

M4-Ext

FULL MODULATION SEQUENCING EXTENSION

M4-LHS

STAGE

MENU

OD=35

o

F

<<A>>

B

100%

50%

SYS=145

o

F

M4-LHS

CONDENSING AND NON-CONDENSING

4-20 mA EMS

4-20mA INPUT

+

Signal GND

1

2

3

RS485

EXTENSION

CONNECTORS

X SIG

(-)

EMS/BMS Sources

Excitation Voltage

(+)

EMS/BMS

Temperature

Set PointInput

M4-LHS connected to Two Extension

Panels and 4-20mA EMS Interface

Each Extension Panel or 4-20mA EMS

Interface comes with Connection Cable.

RJ11

RJ45 to RJ11

Adaptor

RJ11

RJ11

RJ11