Boost mode, Sensor fault, Setting the control to factory defaults – LAARS M4-LHS - Installation Manual User Manual

Page 25: Alert

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

25

Boost Mode

(Not Available in Setback Mode)

30 Minutes, Disabled

Default: Disable

Button: MENU/<System Startup>/..../Boost Mode

• The morning Boost is designed to return the building to comfortable ambient temperatures

after the cooler Night (Setback) period. The control will accomplish this by running

elevated water temperatures (will add Setback setting to calculated water temperature) for

30 minutes before the start of the Day schedule setting. That is, if the normal day set point

at a specific outdoor was 145˚F and the Setback setting was 20˚F, the boost will raise the

system calculated temperature to 165˚F for 30 minutes before the start of the Day Schedule

setting.

• If no Boost is needed, then simply select Disabled from the Boost Menu.

• Boost is only available if Shutdown or Tstat is selected as an option. See previous setting.

--- BOOST MODE ---

30 Minutes

Disable

BACK ▲ ▼ SAVE

Sensor Fault

All Off, All On

Default: All On

Button: MENU/<System Startup>/..../Sensor Fault

• The Sensor Fault will determine the operating status of all output stages that has their Mode

set to Auto when a sensor reads Short or Open.

• When All-Off is selected, the control will turn all boilers Off when the System sensor reads

Short or Open. However, when the Outdoor sensor reads Short or Open, the control will try

to maintain the Minimum Water Temperature.

• When All-On is selected and the Boiler Type was set to other than Hybrid, the control will

turn all boilers On to a 100% when the System sensor reads Short or Open and the outdoor

temperature is below Outdoor Cutoff. However, when the Outdoor sensor reads Short or

Open, the control will try to maintain the Maximum Water Temperature.

• When All-On is selected and the Boiler Type was set to Hybrid, the control will turn all

Non-Condensing boilers On to full fire when the System sensor reads Short or Open and the

outdoor temperature is below Outdoor Cutoff. During that time all Condensing boilers will

turn Off. When the Outdoor sensor reads Short or Open, the control will try to maintain the

Maximum Water Temperature.

--- SENSOR FAULT ---

All Off

All On

BACK ▲ ▼ SAVE

aLErT

A good practice after performing

any Startup menu modification

is to check all operating settings

and adjustments to match the new

settings.

SETTiNg THE CONTrOL TO FaCTOrY DEFauLTS

To Reset the M4-LHS control to its original factory defaults, power down the control.

Hold down the two right most buttons while powering the control back up until the
TOTAL CLEAR STARTED screen appears. The Display will direct you to the Startup

menu to program the control after the defaults are loaded.

TOTAL CLEAR STARTED

Release buttons

and

Please Wait

NOTE: When resetting the control to original factory defaults all control settings will be

overwritten and will no longer exist.

aLErT

Do not turn off power to control until all Startup settings have been made. Otherwise, the next

power-up will be set to many Startup factory settings that may not fit your application.