Mode, M4-lhs, Alert – LAARS M4-LHS - Installation Manual User Manual

Page 39: A b c d, Hybrid control mode

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

39

OD=

55

o

F SYS=

143

o

F

<<A>>

B

67%

20%

STAGE ◄ ► MENU

STAGE A SETTINGS

Mode

Auto

<Prev Stage>

<Next Stage>

BACK ▲ ▼ SELECT

STAGE A SETTINGS

Mode

Auto

Ignition %

1%

Mod Start %

80%

<Prev Stage>

<Next Stage>

Copy Settings

BACK ▲ ▼ SELECT

STAGE A MODE

Auto

Standby

Manual

Off

On

BACK ▲ ▼ SAVE

STAGE A

- IGNITION POINT -

1%

[

]

BACK ▲ ▼ SAVE

STAGE A

MODULATION START

75%

[

]

BACK ▲ ▼ SAVE

Staging

Modulation

Button: STAGE/

The Stage menu provides adjustment for each of the individually boiler operations.

• In most installations, all active boiler adjustments are the same, but each can be configured

differently if desired.

• If the boilers are not set up properly, the M4-LHS operation may appear to be erratic.

• When the STAGE button is depressed, the Boiler A settings menu will be shown.

• Make all the appropriate settings for Boiler A (See below).

• After completing all the settings for Boiler A (See below), you have the option of copying

these settings to all other modulating boilers. Everything but the Mode -- Auto/Standby/

Manual/Off/On -- will be copied.

• Then select the <Next Stage> option from the menu to reach the Boiler B settings

menu. Continue until all boilers have been set.

• If an Extension is connected to the M4-LHS and the stages have been set through the

Startup menu, then scrolling through stages using the <Next Stage> and <Prev
Stage> menu options will scroll through the Extension stages as well.

aLErT

To change the M4-LHS settings, the Program/Run Switch must be set to

Program. The switch is located under the Enclosure Wiring Cover for security.

The Enclosure Wiring Cover can be secured using a lock.

Modulating Boiler Stage Menu

STAGE A SETTINGS

Mode

Auto

Ignition %

1%

Mod Start %

80%

<Prev Stage>

<Next Stage>

Copy Settings

BACK ▲ ▼ SELECT

Sequencing Boiler Stage Menu

STAGE A SETTINGS

Mode

Auto

<Prev Stage>

<Next Stage>

BACK ▲ ▼ SELECT

SYSTEM

A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

/TSTAT

M4-LHS

HYBRID CONTROL

Mode

Auto, Standby, Manual, Off, On

Default: Auto

Button: STAGE/Mode

• The M4-LHS only controls the modulation of boilers set to Auto or (after a delay) those

set to Standby. None of the other settings is recommended for outputs connected to active

boilers.

• Any stage without an active boiler or stage connected must be set to Off.

• The following list describes the MODE options:

STAGE A MODE

Auto

Standby

Manual

Off

On

BACK ▲ ▼ SAVE