A

M4-LHS installation and Operation Manual

27

OPEraTiNg SETTiNgS

Program Change Switch Setting

To be able to change the M4-LHS settings, the Program/Run Switch must be set to Program.

The switch is located under the Enclosure Wiring Cover for security.

SYSTEM

A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

/TSTAT

M4-LHS

HYBRID CONTROL

Season

Winter, Summer

Default: Winter

Button: MENU/Season

• The M4-LHS will turn all boiler relays off when it is in Summer setting. However, an

indirect DHW call will bring boilers back on when needed. The Message Display Line will

display Summer to show the status.

• In Winter, the M4-LHS will activate the System relay whenever the Outdoor Temperature

(OD) falls below the Outdoor Cutoff setting. The Message Display Line will not show any

season information when in Winter.

• When the heating season is over, it is a good practice to switch the M4-LHS to Summer

setting. This will allow the control to sequence the boilers on an indirect DHW call.

----- SEASON -----

Winter

Summer

BACK ▲ ▼ SAVE

aLErT

DO NOT turn power off to the

M4-LHS when heating season

is over. If you do so, the battery

will run down and will have to

be replaced. Instead, switch to

Summer.

Set Point

Adjustable 70ºF - 250ºF

Default: 70ºF

(Not Available for Hybrid Boiler Types)

Button: MENU/Set Point

• The Set point is the temperature value the M4-LHS will use to control the system.

• The M4-LHS will increase, decrease or hold the modulation of the boilers to maintain the

system temperature around the Set point.

• The system can be expected to fluctuate around the set point. The amount of fluctuation

depends on the modulation settings and stage Settings.

• If the EMS Input Mode was Enabled, the Set Point will be set by the EMS system and will

be available to be read but not changed on the display. See "EMS Input Mode" on page 19.

----- SET POINT -----

0

o

F

[

]

BACK ▲ ▼ SAVE

reset ratio

Adjustable 1.00ºOD : 4.00ºSys to 4.00ºOD : 1.00ºSys

Default: 1.00ºOD : 1.00ºSys

Button: MENU/System Target

• The Reset Ratio determines how the System water temperature (SYS) will vary with

Outdoor Temperature (OD). With any of the ratios, the colder it becomes outside, the hotter

the temperature of the system water. See "Outdoor Reset Concept" on page 5.

• With a 1.00 (OD):4.00 (SYS) ratio, the System water temperature (SYS) will increase

rapidly as the outside temperature falls, hitting the maximum of 240°F at 24°F outside

temperature. With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS) will

increase slowly as the outside temperature falls. Even at -30°F, the system water will only

be 125°F, and at 24°F outside, the system water will be 112°F. Such a low Reset Ratio

might be used with radiant floor heating applications.

• With most baseboard heating applications, a 1.00 (OD):1.00 (SYS) setting is a good place to

start. With a 1.00 (OD):1.00 (SYS) ratio, for every degree the outside temperature falls, the

system water temperature is increased one degree.

• If required: Adjust the RESET RATIO in cold weather. If the ambient building

temperatures are too low in cold weather, move the ratio to a higher selection. That is,

if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25

(SYS). If the building temperatures are too warm in cold weather, move the ratio to a lower

selection. That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to

1.25 (OD):1.00 (SYS).

-- SYSTEM TARGET --

1.00

o

OD = 4.00

o

Sys

1.00

o

OD = 3.00

o

Sys

1.00

o

OD = 2.00

o

Sys

1.00

o

OD = 1.50

o

Sys

1.00

o

OD = 1.25

o

Sys

1.00

o

OD = 1.00

o

Sys

1.25

o

OD = 1.00

o

Sys

1.50

o

OD = 1.00

o

Sys

2.00

o

OD = 1.00

o

Sys

3.00

o

OD = 1.00

o

Sys

4.00

o

OD = 1.00

o

Sys

BACK ▲ ▼ SAVE

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

110

100

90

80

Outdoor Temperature

W

at

er

Te

m

pe

ra

tu

re

70

40

50

60

150

140

130

120

1:4

With a 0° Offset, the
Reset curves begin at
100° Water Temperature.

With a -20° Offset, the
Reset curves begin at
80° Water Temperature.

With a +20° Offset, the
Reset curves begin at
120° Water Temperature.

1:4

1:4

1:1

1:1

1:1

4:1

4:1

4:1

90

100

+20 Offset

-20 Offset

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

1:4

1:1

4:1

Colder

Warmer

reset ratio