HT# 059295-00

A

M4-LHS installation and Operation Manual

41

TrOuBLESHOOTiNg

SENSOr iNPuTS

Display shows Sensor OPEN or SHOrT

When the display shows sensor OPEN, short the control sensor input terminals. The display

should change to read SHORT. This indicates that the sensor wires are not continuous. If the

display does not SHORT, the M4-LHS may be damaged.

When the display shows sensor SHORT, remove the wires from the sensor terminals. The

display should change to read OPEN. In this case, replace the sensor. Otherwise, if the display

does not show OPEN, the M4-LHS may be damaged.

Display shows an incorrect Temperature

Remove the wires from the sensor terminals. The display should change to read OPEN. If it

does not, the M4-LHS may be damaged. Take an ohm reading across the detached sensor wires.

The ohm reading should correspond to the Temperature Sensor Chart. If it does not, the sensor

may be damaged.

Temperature Sensor Chart

TEMPEraTurE

Value

(in Ohms)

°

F

°

C

OPEN

150000

-30

-34

117720

-20

-29

82823

-10

-23

59076

0

-18

42683

10

-12

31215

20

-7

23089

25

-4

19939

30

-1

17264

35

2

14985

40

4

13040

45

7

11374

50

10

9944

55

13

8714

60

16

7653

70

21

5941

80

27

4649

90

32

3667

100

38

2914

110

43

2332

120

49

1879

130

54

1524

140

60

1243

150

66

1021

160

71

842

170

77

699

180

82

583

190

88

489

200

93

412

210

99

349

220

104

297

230

110

253

240

116

217

250

121

187

SHORT

100

CONTrOL OPEraTiON

No Heat

• Season - Make sure that the Season is set to Winter. See "Season" on page 27 and "Display

Messages" on page 38.

• Prove - Even though, the system relay may be energized, the M4-LHS will not energize and

stage relays unless the Prove is shorted. See "Display Messages" on page 38 and "Wiring the

Prove" on page 13.

• Shutdown - The M4-LHS will deactivate stage outputs when the Shutdown terminals are

shorted. See "Display Messages" on page 38 and "Wiring the Shutdown, Tstat, or Setback" on

page 12.

• Tstat - The M4-LHS will deactivate stage outputs when the Tstat terminals are open. See

"Display Messages" on page 38 and "Wiring the Shutdown, Tstat, or Setback" on page 12.

• Sensor Fault - When the Sensor Fault is set to All Off in the startup menu, the System sensor

fault (in all Sensor Type modes) or the Outdoor sensor fault (in Reset mode) will de-energize all

stage relays. See "Display Messages" on page 38 and "Sensor Fault" on page 25.

• System or Outdoor Sensor - If the System or Outdoor sensor reading was higher that the actual

temperature, the M4-LHS might not bring any stage on. Check "Display shows an Incorrect

Temperature" section.

• Outdoor Cutoff - If the Outdoor cutoff was set too low, the building might be allowed to

cool more than is desired. A comfortable setting is between 60°F to 65°F. "Outdoor Cutoff

Temperature" on page 30

Too Much Heat

• Indirect Domestic Hot Water call - The M4-LHS will raise the temperature of the system to the

DHW Set Point on a DHW call, connected to terminals 29 and 30. Check to see if there is a call

for DHW and the length of time it lasts.

• Reset Ratio and Offset - If excessive heat occurs only in certain weather conditions, adjust the

Reset Ratio and Offset. See "Outdoor Reset Concept" on page 5. If excessive heat occurs year

round, reduce the Offset.

• Boiler Mode Settings - The M4-LHS will only controls boilers their mode is set to Auto or

Standby. Check if any boiler stage is set to Manual or On. See "Mode" on page 39.

• Control Settings - The Last Stage Hold will allow only the Lead boiler to stay on for an

additional number of degrees. If the setting is too high, and only the Lead boiler is on, the

system can over heat. Reduce the Last Stage Hold setting. See"Last Stage Hold" on page 32.