196

Motion Control Theory

When software limit signal is set to ON status the controller

responses with following actions:

1. If SPEL signal is asserted for an axis in positive direction

motion status, the controller stops motion of the axis

immediately and error stop code of the axis is set to "6"

(STOP_SPEL) and motion status of axis is set to

abnormal stop (ASTP).

2. If SMEL signal is asserted for an axis in negative

direction motion status, the controller stops motion of the

axis immediately and error stop code of the axis is set to

"7" (STOP_SMEL) and motion status of axis is set to

abnormal stop (ASTP).

3. If the axis is not in motion status and the SPEL signal is

asserted then user's positive direction motion command

shall be ignored by the controller while error stop code of

the axis is set to STOP_SPEL (6) and motion status of

axis is set to abnormal stop (ASTP).

4. If the axis is not in motion status and the SMEL signal is

asserted then user's negative direction motion command

shall be ignored by the controller while error stop code of

the axis is set to STOP_SPEL (7) and motion status of

axis is set to abnormal stop (ASTP).

4.11.2.2

Position Error Protection

Position error protection is a software protection mechanism by

monitoring difference between command counter and feedback

counter. This difference is defined as position error. When position

error is too big, the controller sends a Servo off signal which can

be set up for use before servo fine tuning.
This function can be set up with axis parameters as shown in table

below. You can disable the position error protection by setting

position error parameter (PRA_ERR_POS_LEVEL) to value "0".

The position error protection is enabled when position error

parameter is set to non-zero value.

Position error protection causes the controller responses with

following actions:
If the position error value is greater than setting given by users,

the controller run Servo off command directly and error Stop code

of the axis is set to STOP_ERROR_LEVEL (6) and motion status

of axis is set to abnormal stop (ASTP).

NO

Define

Description

124h

PRA_ERR_POS_LEVEL

Position error protection setup