11

Figure 8. Elements of the Signal Name Using Product Naming

Figure 9 shows an example of an IED (SB1) with logical devices LD1 and LD2. Each logical device (LD1
and LD2) contain logical nodes LN1 and LN2, which control a circuit breaker QA1 of bay Q1 in voltage
level E1.

Figure 9. Names within Different Structures of the Object Model

Communication Network Section

The organization of the physical IEDs to the communication network is independent of the substation
structure. The IEC 61850 standard defines the communication network with no relation to an existing
media and protocol. The first mapping to an existing media and protocol is done in IEC 61850–8–1 with:

Ethernet as medium

MMS (Manufacturing Message Specification) protocol as defined in ISO 9506–1 and ISO 9506–2

The IEC 61850 standard describes in part 7–2 the Abstract Communication Service Interface (ACSI) in a
media and protocol independent form. Part 8–1 specifies the mapping of this ACSI to the existing MMS.

The communication section in the SCL file describes the minimum of what is needed to identify how
information is routed between the IEDs in a project. This is:

the used sub networks

the IEDs connected to the different sub networks

LN Prefix

LN Class

LN Instance #

LNName

LDName

IED Section:

Attribute Name of

element IED

IED Section:

Attribute Inst of

element LDevice

IED Section:
Attribute Inst of element LN

Defined in IEC 61850-7-4

Predefined by IED

Header:
NameStructure=”IEDName”

P

0

0

6

1

-6

3

E1

Q1

QA1

SB1

LD1

LD2

LN1

LN2

LN1

LN2

W1

Voltage Level

Bay

IED

Access Point

Station Bus

S1

In the communication
structure
, this connection is
identified as W1E1Q1SB1S1.

In the IED structure, this LD
is identified as -E1Q1SB1LD2.

In the IED (product)
structure
, this LN is identified
as -E1Q1SB1LD2CSWI2.

In the substation structure,
this LN is identified as
=E1Q1LD2QA1CSWI2.

In the substation structure,
this CBR is identified as
=E1Q1QA1.

P

0

0

6

1

-6

4

BE1-11

IEC 61850 Engineering