Basler Electric BE1-11 IEC 61850 Protocol User Manual

Page 91

Advertising
background image

9424200892 Rev F

83

Description

Value / Clarification

Pre-configured RCB attributes that cannot be
changed online when RptEna = FALSE
(see also the ICD report settings)

<configuration revision>

May the reported data set contain:
- structured data objects?
- data attributes?
- timestamp data attributes?


Y
Y
Y

What is the scan cycle for binary events?
Is this fixed, configurable?

4 msec
Fixed

Table 27. PIXIT for Generic Substation Events Model

Description

Value / Clarification

What elements of a subscribed GOOSE header
are checked to decide the message is valid and
the allData values are accepted? If yes, describe
the conditions.
Note: the VLAN tag may be removed by a
Ethernet switch and should not be checked

N source MAC address
Y destination MAC address
Y Ethertype = 0x88B8
Y gocbRef
N timeAllowedtoLive
Y datSet
N goID
N t
N stNum
N sqNum
N test
Y confRev
Y ndsCom
Y numDatSetEntries
N AppID

Can the test flag in the published GOOSE be
turned on / off ?

N

What is the behavior when the GOOSE publish
configuration is incorrect ?

DUT keeps GoEna=F

When is a subscribed GOOSE marked as lost?
(TAL = time allowed to live value from the last
received GOOSE message)

n/a

What is the behavior when one or more
subscribed GOOSE messages isn’t received or
syntactically incorrect (missing GOOSE)?

use last received Goose until timeout occurs, then
device will switch to the default value input from
logic for each GGIO

What is the behavior when a subscribed GOOSE
message is out-of-order?

use last received Goose until timeout occurs, then
device will switch to the default value input from
logic for each GGIO

What is the behavior when a subscribed GOOSE
message is duplicated?

use last received Goose

Does the device subscribe to GOOSE messages
with/without the VLAN tag?

Y with the VLAN tag
Y without the VLAN tag

May the GOOSE data set contain:
- structured data objects?
- data attributes?
- timestamp data attributes?

Subscribed

N

Y

N

What is the slow retransmission time?
Is it fixed or configurable?

30,000 msec with TAL = 60,000
Configurable

BE1-11

Conformance Statements

Advertising