Configuration Example

This configuration example provides step-by-step instructions on how to configure two separate CIDs.

Configure Communication Parameters and Names

Step 1: Start BEST61850 software.

Step 2: Using the mouse, left-click on and hold the BE1-11 SCL Template. While holding down the left

mouse button, drag the template into the Workspace area and release. See Figure 24.

Step 3: The BE1-11 BEST61850 Template Selection screen appears as shown in Figure 25. Use the

drop-down buttons to select the style number of the BE1-11 and click OK.

Step 4: Under IED Properties, enter BE1_11_1 for IED Name and Protective Relay 1 for Description.

Enter the IED Network Settings for the IED being configured.

Step 5: The CID should be validated against the ICD file before proceeding. Right-click on the

BE1_11_1 file in the Workspace and select Validate. The round indicator located on the left
side of the file name changes from yellow to green if validation is successful.

Step 6: Repeat Steps 2 and 3 to add a second SCL Template to the Workspace. See Figure 26.

Step 7: Under IED Properties, enter BE1-11_2 for IED Name and Protective Relay 2 for Description.

Enter the IED Network Settings for the IED being configured.

Step 8: Right-click on the BE1_11_2 file in the Workspace and select Validate. The round indicator

located on the left side of the file name changes from yellow to green if validation is successful.