Basler Electric BE1-11 IEC 61850 Protocol User Manual

Page 48

Advertising
background image

42

9424200892 Rev F

Figure 41. MMXUN and MSQI Measurement Node Default Deadband Values

Table 14. Summary of BE1-11 IEC 61850 Parameter Limits

Parameter

Limit

Description

Maximum number of DataSets

16

Max number of different named DataSets

Maximum number of bytes for
single Goose Message

1400

Max number of bytes allowed in one Goose Message
from selected DataSets

Maximum number of Published
Goose Messages

4

Max number of sent Goose Control Blocks messages

Maximum number of Subscribed
Goose Messages

20

Max number of received Goose Messages mapped to
Single Point Control SPCSO# inputs

Maximum number of Report
Control Blocks supported

8

Max number of configured reports a single client can
request

Maximum number of Clients per
RCB
(Report Enabled Max)

4

Max number of different clients that can request Report
Control Blocks

BEST61850™

BE1-11