Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 48
42
9424200892 Rev F
Figure 41. MMXUN and MSQI Measurement Node Default Deadband Values
Table 14. Summary of BE1-11 IEC 61850 Parameter Limits
Parameter
Limit
Description
Maximum number of DataSets
16
Max number of different named DataSets
Maximum number of bytes for
single Goose Message
1400
Max number of bytes allowed in one Goose Message
from selected DataSets
Maximum number of Published
Goose Messages
4
Max number of sent Goose Control Blocks messages
Maximum number of Subscribed
Goose Messages
20
Max number of received Goose Messages mapped to
Single Point Control SPCSO# inputs
Maximum number of Report
Control Blocks supported
8
Max number of configured reports a single client can
request
Maximum number of Clients per
RCB
(Report Enabled Max)
4
Max number of different clients that can request Report
Control Blocks
BEST61850™
BE1-11