74

9424200892 Rev F

BE1-11f

BE1-11i

BE1-11g

BE1-11t

BE1-11m

Overvoltage : PTOV1, PTOV2, PTOV3, PTOV4

59P-1 to 4

59P-1 to 4

59P-1 to 4

59P-1 to 4

59P-1 to 2

Overvoltage : PTOV5, PTOV6, PTOV7, PTOV8

59X-1 to 4

59X-1 to 4

59X-1 to 4

59X-1 to 4

59X-1 to 2

Motor Restart Inhibition: PMRI1

66

Phase Angle Measuring: P78VPPAM1

78V

78V

Phase Angle Measuring:P78OOSPPAM1

78OOS

Under Frequency : PTUF1, PTUF2, PTUF3, PTUF4

81-1 to

81-4

81-1 to

81-4

81-1 to

81-4

81-1 to

81-4

81-1, 81-2

Over Frequency : PTOF1, PTOF2

81-5, 81-6

81-5, 81-6

81-5, 81-6

81-5, 81-6

Over Frequency : PTOF3, PTOF4

81-3 , 81-4

Rate Of Change Frequency : PFRC1, PFRC2

81-7, 81-8

81-7, 81-8

81-7, 81-8

81-7, 81-8

Differential protection: P87NPDIF1

87N

optional

87N-1,

87N-2

Differential protection: P87PDIF1

87 optional

87

87 optional

Protection Trip Conditioning : PTRC1

Logic

Points

Logic

Points

Logic

Points

Logic

Points

Logic

Points

R: Protection related functions

Sync-check : RSYN1

25

25

25 optional

Auto synchronizer: P25ARSYN1

25A

optional

Breaker failure : RBRF1

50BF

50BF

50BF

50BF

50BF

Automatic reclosing : RREC1

79

79

Fault locator : RFLO1

FLT

FLT

FLT

FLT

FLT

Disturbance Recorder Function: RDRE

FLT

FLT

FLT

FLT

FLT

G: Generic References

Generic Process Control Inputs : CTLGGIO1,
CTLGGIO2, CTLGGIO3, CTLGGIO4

Input

Logic

Points

Input

Logic

Points

Input

Logic

Points

Input

Logic

Points

Input

Logic

Points

Generic Process Indicator Outputs : INDGGIO1,
INDGGIO2, INDGGIO3, INDGGIO4

Output

Logic

Points

Output

Logic

Points

Output

Logic

Points

Output

Logic

Points

Output

Logic

Points

M: Metering and Measurement

Multi-Phase Measurement : MMXU1
CT Circuit 1

Amps,

Volts,

Power,

Freq

Amps,

Volts,

Power,

Freq

Amps,

Volts,

Power,

Freq

Amps,

Volts,

Power,

Freq

Amps,

Volts,

Power,

Freq

Multi-Phase Measurement : IABCMMXU1
CT Circuit 1

Amps

Amps

Amps

Amps

Amps

Multi-Phase Measurement : IABCMMXU2
CT Circuit 2

Amps

optional

Amps

optional

Amps

optional

Amps

Amps

Single Phase Measurement : VXMMXN1

VX

VX

VX

VX

VX

Single Phase Measurement : IGMMXN1
CT Circuit 1

IG or IG1

IG or IG1

IG or IG1

IG or IG1

IG or IG1

Single Phase Measurement : IGMMXN2
CT Circuit 2

IG2

optional

IG2

optional

IG2

optional

IG2

IG2

Sequence Components : MSQI1
CT Circuit 1

I0, I1, I2,

V0, V1, V2

I0, I1, I2,

V0, V1, V2

I0, I1, I2,

V0, V1, V2

I0, I1, I2,

V0, V1, V2

I0, I1, I2,

V0, V1, V2

Sequence Components : MSQI2
CT Circuit 2

I0, I1, I2

I0, I1, I2,

I0, I1, I2

I0, I1, I2

I0, I1, I2

X: Switchgear

Circuit breaker : XCBR1

52a, 52b

Trip &

Close Coil

52a, 52b

Trip &

Close Coil

52a, 52b

Trip &

Close Coil

52a, 52b

Trip &

Close Coil

52a, 52b

Trip &

Close Coil

Conformance Statements

BE1-11