Configure datasets – Basler Electric BE1-11 IEC 61850 Protocol User Manual

Page 35

Advertising
background image

9424200892 Rev F

29

Figure 25. BE1-11 BEST61850 Template Selection Screen

Figure 26. Adding a Second SCL Template to the Workspace

Configure DataSets

Step 1: Select the DataSets tab in BEST61850. See Figure 27. A maximum of 16 DataSets is allowed.

Step 2: Highlight the BE1_11_1 file in the Workspace and click the New Dataset button. The Add New

Dataset screen appears. See Figure 28.

Step 3: Enter a dataset description and select PRO$INDGGIO1$ST$Ind01$stVal by selecting the

individual parts of the FCDA (Functionally Constrained Data Attribute) information as shown in
Figure 28. The FC (Functional Constraint) is automatically set to ST.

Step 4: Click the Add

 button to add the FCDA information to the current FCDA.

Step 5: Click the Add button in the lower-right corner of the Add New Dataset window.

BE1-11

BEST61850™

Advertising