Basler Electric BE1-11 IEC 61850 Protocol User Manual

Page 84

Advertising
background image

76

9424200892 Rev F

Table 20. ACSI Models Conformance Statement

Client/subscriber

Server/publisher

Value/comments

IF SERVER SIDE (B11) SUPPORTED

M1

Logical device

c2

c2

Yes

M2

Logical node

c3

c3

Yes

M3

Data

c4

c4

Yes

M4

Data set

c5

c5

Yes

M5

Substitution

O

O

No

M6

Setting group control

O

O

Yes

REPORTING

M7

Buffered report control

O

O

Yes

M7-1

sequence-number

Yes

M7-2

report-time-stamp

Yes

M7-3

reason-for-inclusion

Yes

M7-4

data-set-name

Yes

M7-5

data-reference

Yes

M7-6

buffer-overflow

Yes

M7-7

entryID

Yes

M7-8

BufTm

Yes

M7-9

IntgPd

Yes

M7-10

GI

Yes

M8

Unbuffered report
control

O

O

Yes

M8-1

sequence-number

Yes

M8-2

report-time-stamp

Yes

M8-3

reason-for-inclusion

Yes

M8-4

data-set-name

Yes

M8-5

data-reference

Yes

M8-6

BufTm

Yes

M8-7

IntgPd

Yes

M8-8

GI

Yes

Logging

M9

Log control

O

O

No

M9-1

IntgPd

No

M10

Log

O

O

No

M11

Control

M

M

Yes

IF GSE (B31/32) IS SUPPORTED

GOOSE

O

O

Yes

M12-1

entryID

No

M12-2

DataReflnc

No

M13

GSSE

O

O

No

Conformance Statements

BE1-11