Signal engineering, Dataset – Basler Electric BE1-11 IEC 61850 Protocol User Manual

Page 20

Advertising
background image

14

9424200892 Rev F

Signal Engineering

Signal engineering consists of DataSets, Report Control Blocks (RCB), and Goose Control Blocks
(GoCB).

DataSets

IEC 61850 has defined DataSets for signal transmission in Report Control Blocks. DataSets are also used
for GOOSE messages. Figure 12 shows a DataSet where all position information of the apparatuses of a
bay are put into one DataSet.

Figure 12. DataSet Example

General rules for DataSet configuration:

All data objects or their data attributes can be selected for a DataSet.

Only those data attributes of a data object are selected which have the same functional constraint
(FC).

Data objects with different FC can be selected for a DataSet. For example DOs with FC=ST and
DOs with FC=MX can be members in one DataSet.

A single data attribute can be selected when it is specified with a trigger option. For example the
data attribute stVal of the data object Pos can be selected as a member of a DataSet, because it
is specified with the trigger option data change detected (dchg).

The description of the DataSets and the list of data object members or FCDAs (Functionally Constrained
Data Attributes) is included in the SCL file in the IED section in the Logical Device subsection. FCDAs are

P

0

0

6

1

-6

7

LD1

LLN0

LPHD

SXCBR1

SCSWI1

SXSWI1

SCSWI2

SXSWI2

SCSWI3

SXSWI3

SCSWI4

SXSWI4

SCSWI5

CVMMXU1

Pos

Pos

Pos

Pos

Pos

stVal

q

t

Origin

LD1/LLN0

LD1/SXCBR1.Pos FC=ST

LD1/SXSWI1.Pos FC=ST

LD1/SXSWI2.Pos FC=ST

LD1/SXSWI3.Pos FC=ST

LD1/SXSWI4.Pos FC=ST

DataSet

IEC 61850 Engineering

BE1-11

Advertising