The BE1-11 is capable of transmitting the following items on an IEC 61850 network:

Configuration Settings

Metering

Status

Alarms

Targets

Breaker Operations

Direct Control

Fault Records

Load Profile

Oscillographic Records

Sequence of Events Reports

Unsolicited Reports

Peer to Peer Control GOOSE

Device Discovery

IEC 61850 Configuration

IEC 61850 Standard

The IEC 61850 standard defines the parts for communicating information between IEDs in a substation.

Figure 2 illustrates the Basler IEC 61850 configuration process.

Figure 2. Basler IEC 61850 Configuration Process

BESTCOMSPlus

®

BESTCOMSPlus software is provided with the BE1-11. Refer to the BESTCOMSPlus chapter for more
information.

BESTCOMSPlus performs the following tasks:

Maps BE1-11 inputs and outputs to IEC 61850 data points that can be read directly with an IEC
61850 browser

Uses a point-and-click method to configure BE1-11 settings and logic

Uploads and downloads BE1-11 settings files

Provides metering and reports from the BE1-11

Substation

Configuration Tool

SCD file

Basler

BEST61850

Validate SCL

and Map GOOSE

Basler

BE1-11 System

Basler

BESTCOMSPlus®

Create relay settings BSTX file