Pics – Basler Electric BE1-11 IEC 61850 Protocol User Manual

Page 83

Advertising
background image

9424200892 Rev F

75

BE1-11f

BE1-11i

BE1-11g

BE1-11t

BE1-11m

Z: Other

Motor: ZMOT

Output

Logic Point

PICS

The following ACSI conformance statements are used to provide an overview and details about the
BE1-11 Protection System.

ASCI basic conformance statement (Table 19)

ACSI models conformance statement (Table 20)

ACSI service conformance statement (Table 21)

The statements specify the communication features mapped to IEC 61850-8-1.

Table 18. Conformance Statement Key and Notes

Table Entry

Description

Yes

Supported with MMS services and objects necessary for implementing this capability.

No

Not supported.

Not applicable.

Table 19. ACSI Basic Conformance Statement

Client/subscriber Server/publisher Value/comments

CLIENT-SERVER ROLES

B11 Server side (of two-party

application-association)

c1

Yes

B12 Client side (of two-party

application-association)

c1

No

SCSMS SUPPORTED

B21 SCSM: IEC 61850-8-1 used

Yes

B22 SCSM: IEC 61850-9-1 used

No

B23 SCSM: IEC 61850-9-2 used

No

B24 SCSM: other

No

GENERIC SUBSTATION EVENT MODEL (GSE)

B31 Publisher side

O

Yes

B32 Subscriber side

O

Yes

TRANSMISSION OF SAMPLED VALUE MODEL (SVC)

B41 Publisher side

O

No

B42 Subscriber side

O

No

Notes:
c1 - shall be 'M' if support for LOGICAL-DEVICE model has been declared.
O - Optional
M - Mandatory


BE1-11

Conformance Statements

Advertising