78

9424200892 Rev F

SERVICES

AA:

TP/MC

Client/

subscriber

Server/

publisher

Value/

comments

SETTING GROUP CONTROL

S18

SelectActiveSG

TP

O

O

Yes

S19

SelectEditSG

TP

O

O

No

S20

SetSGValues

TP

O

O

No

S21

ConfirmEditSGValues

TP

O

O

No

S22

GetSGValues

TP

O

O

No

S23

GetSGCBValues

TP

O

O

No

REPORTING

BUFFERED REPORT CONTROL BLOCK (BRCB)

S24

Report

TP

c6

c6

Yes

S24-1

data-change (dchg)

Yes

S24-2

qchg-change (qchg)

Yes

S24-3

data-update (dupd)

Yes

S25

GetBRCBValues

TP

c6

c6

Yes

S26

SetBRCBValues

TP

c6

c6

Yes

UNBUFFERED REPORT CONTROL BLOCK (URCB)

S27

Report

TP

c6

c6

Yes

S27-1

data-change (dchg)

Yes

S27-2

qchg-change (qchg)

Yes

S27-3

data-update (dupd)

Yes

S28

GetURCBValues

TP

c6

c6

Yes

S29

SetURCBValues

TP

c6

c6

Yes

LOGGING

LOG CONTROL BLOCK

S30

GetLCBValues

TP

M

M

No

S31

SetLCBValues

TP

M

M

No

LOG

S32

QueryLogByTime

TP

c7

M

No

S33

QueryLogByEntry

TP

c7

M

No

S34

GetLogStatusValues

TP

M

M

No

GENERIC SUBSTATION EVENT MODEL (GSE)

GOOSE-CONTROL-BLOCK

S35

SendGOOSEMessage

MC

c8

c8

Yes

S36

GetReference

TP

O

c9

No

S37

GetGOOSEElementNumber

TP

c9

c9

No

S38

GetGoCBValues

TP

O

O

Yes

S39

SetGoCBValues

TP

O

O

Yes