VCM-X / RNE Operator Interface SD

VCM-X CONFIGURATION

27

VCM-X Confi guration Screens

Confi guration Screen #9 - Outdoor Humidity

Sensor

VCM-X Cnfg ID 59

Outdoor Humidity

Sensor: NO

Use < Or > To Change

Select YES if the HVAC unit is equipped with an Outdoor Air Humidity
Sensor. Default is NO.

Confi guration Screen #10 - Indoor Humidity

Sensor

VCM-X Cnfg ID 59

Indoor Humidity

Sensor: NO

Use < Or > To Change

Select YES if the HVAC unit is equipped with an Indoor Air Humidity
Sensor. Default is NO.

Confi guration Screen #11 - Heat During

Dehumidify

VCM-X Cnfg ID 59

Heat During

Dehumidify: NO

Use < Or > To Change

Select YES if your application needs to use unit heat during Dehumidi-
fi cation to supplement Reheat. If Reheat is not available, this selection
will allow unit heat to operate in place of Reheat. Default is NO.

Confi guration Screen #12 - Economizer

Control

VCM-X Cnfg ID 59

Economizer

Control: NO

Use < Or > To Change

Select YES if the VCM-X is controlling the Economizer. Default is NO.

Confi guration Screen #13 - Title 24 Economizer

VCM-X Cnfg ID 59

Title 24

Economizer: NO

Use < Or > To Change

If this unit has Title 24 Economizer operation, this option should be
confi gured as YES. Default is NO.

Confi guration Screen #14 - Proof of Flow Input

VCM-X Cnfg ID 59

Proof Of Flow

Input: NO

Use < Or > To Change

Select YES if the unit is equipped with a Proof of Flow Switch and it
is connected to the VCM-X. If selected as YES and the Proof of Flow
Switch is open, only the Supply Fan Relay will be active. If any other
relays such as Heating Stages or Cooling Stages are active, they will be
deactivated when the Proof of Flow Switch input is lost. Default is NO.

Confi guration Screen #15 - Modulating Cooling/

Heating

VCM-X Cnfg ID 59

Mod Cooling: NO
Mod Heating: NO

Use < Or > To Change

Select YES if the HVAC unit is controlling Modulating Heating or
Modulating Cooling or both. If your HVAC unit is going to use a Modu-
lating Chilled Water Valve or is equipped with a Digital Compressor,
you must select YES for Modulating Cooling. If your HVAC is using a
Modulating Hot Water Valve, Modulating Steam Valve, or a SCR Con-
trolled Electric Heater, you must select YES for Modulating Heating.
This confi guration does not apply to MODGAS using the MODGAS
Controller. Default is NO.

Confi guration Screen #16 - Modulating

Heating Output Signal

VCM-X Cnfg ID 59

Mod Heating

Output Signal.: 0-10V

Use < Or > To Change

Select 0-10 VDC or 2-10 VDC as the output signal for a Modulating
Heat Source such as a Hot Water Valve or SCR Electric Heater. Default
is 0-10 VDC.