Rne configuration, Rne confi guration screens – Orion System VCM-X/RNE Controller User Manual

Page 41

Advertising
background image

VCM-X / RNE Operator Interface SD

RNE CONFIGURATION

41

Confi guration Screen #41 - Emergency

Shutdown Input

RNE Cnfg ID 101

Emergency Shutdown

Input: NO

Use < Or > To Change

Select YES if a Smoke Detector/Firestat or other Emergency Shutdown
input is connected to the binary input. If the Emergency Shutdown input
is active, the Supply Fan, Heating and Cooling Relay Outputs will be
disabled. Default is NO.

Confi guration Screen #42 - Return Air Bypass

Control

RNE Cnfg ID 101

Return Air Bypass

Control: NO

Use < Or > To Change

Select YES if your HVAC unit requires Return Air Bypass Control for
Dehumidifi cation Reheat. Default is NO.

Confi guration Screen #43 - Broadcast OA Temp

RNE Cnfg ID 101

Broadcast Outdoor

Temperature: NO

Use < Or > To Change

The RNE can broadcast its Outdoor Air Temperature Reading to
other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device is needed in
order for this feature to operate. Select YES to Broadcast the Outdoor
Temperature. Default is NO.

Confi guration Screen #44 - Broadcast OA Humidity

RNE Cnfg ID 101

Broadcast Outdoor

Humidity: NO

Use < Or > To Change

The RNE can broadcast its Outdoor Air Humidity reading to other HVAC
units if they are not equipped with their own Outdoor Air Humidity
sensors. A network communications device is required in order for
this feature to operate. Select YES to Broadcast the Outdoor Humidity.
Default is NO.

Confi guration Screen #45 - Broadcast Supply

Temperature

RNE Cnfg ID 101

Broadcast Supply

Temperature: YES

Use < Or > To Change

This broadcast sends the RNE’s Supply Air Temperature to all Control-
lers on its local loop. This broadcast needs to be confi gured on a VAV
or Zoning System using the RNE with Orion VAV/Zone Controllers. A
network communications device is required in order for this feature to
operate. Select YES to Broadcast the Supply Air Temperature. Default
is YES.

Confi guration Screen #46 - Broadcast Status

Fan & Heat

RNE Cnfg ID 101

Broadcast Status

Fan & Heat: NO

Use < Or > To Change

This broadcast sends the RNE’s Supply Fan and Heating Status to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to
operate. Select YES to Broadcast the Fan & Heat Status. Default is NO.

Confi guration Screen #47 - Broadcast Internal

Time Clock

RNE Cnfg ID 101

Broadcast Internal

Time Clock: NO

Use < Or > To Change

This broadcast sends the time from the RNE’s Internal Time Clock to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to
operate, but can also be used to synchronize all Controllers on the local
loop. Select YES to Broadcast the Internal Time Clock. Default is NO.

RNE Confi guration Screens