Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 59 – Orion System VCM-X/RNE Controller User Manual

Page 59

Advertising
background image

VCM-X / RNE STATUS

VCM-X / RNE Operator Interface SD

59

VCM-X / RNE Status Screens

Status Screen 11 - Indoor RH & Indoor RH

Setpoint

VCM-X / RNE v1.00

Indoor RH....: XXX%
Indoor RH Spt: XXX%

Line 2 Current Indoor Relative Humidity Percentage

If an Indoor Humidity Sensor has been installed and

confi gured on the unit, the current Indoor Air Relative

Humidity Percentage will appear on this line. The installed

Indoor Humidity Sensor can be either a Wall Mounted type

or a Return Air Mounted type. If an Indoor Humidity

Sensor is not installed, this line will display 0%.

Line 3 Current Indoor Relative Humidity Setpoint Percentage

This is the adjustable Indoor Air Relative Humidity

Setpoint Percentage that has been set by the user.

Status Screen 12 - Static Pressure & Output %

VCM-X / RNE v1.00

Static Pr...: X.XX”

Press Output: XXX%

[Optional Output]

Line 2 Current Static Pressure

Requires the installation and wiring of a Duct Static

Pressure Sensor. If you do not have a Duct Static Pressure

Sensor correctly installed and wired to the controller, this

line will display “0.0”.

Line 3 Current Static Pressure Output Signal Percentage

Indicates the output signal percentage being supplied to the

VFD Controller or Bypass Damper Actuator when you

have

confi gured one of these options for your HVAC unit.

If you have not confi gured Duct Static Pressure Control,

this line will display [No Press Out Confg].

Line 4 Indicates That This is An Optional Output

This output may or may not have live data to display.

Status Screen 13 - Economizer %,

OA Wetbulb, and CO

2

Level

VCM-X / RNE v1.00

Economizer.: XXX %
OA Wetbulb.: XX.XºF
CO2 Level.: XXXXPPM

Line 2 Current Economizer Open Percentage

The Economizer is optional. This shows the Outdoor Air

Damper open percentage. If Economizer Control is not

confi gured, it will display 0%.

Line 3 Current Wetbulb/Drybulb Temperature

The Outdoor Air Wetbulb Temperature is optional. To

display the Outdoor Air Wetbulb Temperature, you must

install an Outdoor Air Temperature Sensor (or an Outdoor

Air Temperature Broadcast) and an Outdoor Air Relative

Humidity Sensor. If these conditions exist, this line will

display

the

calculated

Outdoor

Air

Wetbulb

Temperature.

If these conditions do not exist, it will display 0°F.

Line 4 Current CO

2

Level

The

CO

2

Level is optional. You must install and confi gure a

CO

2

Sensor to display the CO

2

Level. If a CO

2

Sensor is not

installed

and

confi gured, this line will display 0 PPM.

Status Screen 14 - Title 24 Economizer

Feedback Status

VCM-X / RNE v1.00

Economizer

Feedback X%

[Only For Title 24]

Line 3 Economizer Feedback Open Percentage

This shows the Outdoor Air Damper open percentage,

whether the unit is confi gured for Title 24 Economizer

Control or simply has a Minimum Outdoor Air Damper

position

confi gured. If Title 24 Economizer Control is not

confi gured, it will display 0%.

Line 4 Indicates That This is Only For Title 24 Economizer

Status Screen 15 - Outdoor Air CFM & Setpoint

VCM-X / RNE v1.00

OA CFM: 0.00 K
OA Sp.: 0.00 K

[Optional Input]

Line 2 Outdoor Air CFM

If an outdoor air airfl ow monitoring station is being used,

this is the current CFM reading of that device. K = 1000

Line 3 Outdoor Air Setpoint

If control of the OA Damper based on CFM is confi gured,

this is the controlling setpoint. K = 1000

Line 4 Indicates That This is An Optional Input

This input may or may not have live data to display.