Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 56 – Orion System VCM-X/RNE Controller User Manual

Page 56: Status

Advertising
background image

VCM-X / RNE STATUS

VCM-X / RNE Operator Interface SD

56

VCM-X / RNE Status Screens

Status

From any menu screen, press

<STATUS>

. The Unit Selection Screen,

shown below, will appear requesting that you enter the unit ID number.

Unit Selection
Enter Unit ID#

Selected ID#: XXXX

*00*

Enter the correct unit ID number of the VCM-X or RNE Controller you
want to view and press

<ENTER>

. You must type in the number, even

if it is “1”. Once communication is established, the *00* at the bottom
will disappear. Then

press

<

>

. You will then see Setpoint Screen #1.

Press

<ENTER>

to save entered data and

press

<

>

to scroll through

the screens.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

Status Screen 1 - Mode

VCM-X / RNE v1.00

Occupied Mode

Vent Mode

02/15/10 05:00 PM

Line 2 Displays one of the following:

Unoccupied Mode Remote FRC Occupied

Occupied

Mode Override

Mode

Holiday

Mode

Zone

Demand!

Forced Schedule Mode OUTPUT FORCE MODE!

SUPPLY AIR CUTOFF! High CO2 Level Mode!

Line 3

Displays one of the following:

Off Mode Dehumid. Mode

Defrost Mode

Vent Mode Cool Dehumid. Mode

Cool Mode Heat Dehumid. Mode

Heat Mode Warm Up Mode

Line 4

Displays one of the following:

MM/DD/YY HH:MM XX (XX = AM or PM)

Fan Starting Delay and then time will display

xx Left in WarmUp (Number of Minutes Left)

Status Screen 2 - Cooling, Heating, Economizer

VCM-X / RNE v1.00

Cooling Enabled
Heating Enabled

Economizer Disabled

Line 2

Displays one of the following:

Cooling

Enabled

Cooling

Disabled

Line 3

Displays one of the following:

Heating

Enabled

Heating

Disabled

Line 4

Displays one of the following:

Economizer Enabled

Economizer

Disabled

NOTE:

On a non-Heat Pump unit confi gured for Make-Up Air

Control, the Heating and Cooling Lockouts are ignored,
so Heating and Cooling will always show enabled.

Status Screen 3 - Mode Enable Temperature &

Mode Cooling and Heating Setpoints

VCM-X / RNE v1.00

Enable Tmp.: XX.XºF
Cool Spt: XX.XºF
Heat Spt: XX.XºF

Line 2 Mode Enable Temperature

Can be the Supply Air Temperature, Return Air

Temperature, Outdoor Air Temperature, or Space

Temperature, depending on which one has been

confi gured as the Mode Enable Sensor.

Line 3

Cooling Mode Setpoint

Based on the current Occupied/Unoccupied Mode

of

operation.

Line 4

Heating Mode Setpoint

Based on the current Occupied/Unoccupied Mode

of

operation.