Rne configuration, Rne confi guration screens, Vcm-x / rne operator interface sd 40 – Orion System VCM-X/RNE Controller User Manual

Page 40

Advertising
background image

RNE CONFIGURATION

VCM-X / RNE Operator Interface SD

40

RNE Confi guration Screens

Confi guration Screen #34 - CO

2

Sensor

Output Signal

RNE Cnfg ID 101

CO2 Sensor

Output Signal: None

Use < Or > To Change

The RNE needs to know what type of CO

2

sensor signal output is being

provided. Select a 0-10 VDC CO

2

sensor signal (standard sensor used)

or a 4-20 mA CO

2

sensor signal. Select None

if no CO

2

sensor is used.

Default is None.

Confi guration Screen #35 - CO

2

Sensor

Maximum Scale

RNE Cnfg ID 101

CO2 Sensor Maximum

Scale: 2000 PPM

Use < Or > To Change

Default is 2000 PPM. The RNE needs to know the CO

2

Sensor scaling

for proper reading of the CO

2

Sensor output. The Standard CO

2

Sensor

should be scaled to 2000 PPM. Select None if no CO

2

sensor is used.

Default is 2000 PPM.

Confi guration Screen #36 - Building Pressure

Modulating Control

RNE Cnfg ID 101

Building Pressure

Mod Control: NO

Use < Or > To Change

Select YES if Modulating Building Pressure Control is needed. Modu-
lating Building Pressure Control is used for a VFD Exhaust Fan or a
Modulating Exhaust Fan Damper Actuator for Direct Acting Building
Pressure Control. Modulating Building Pressure Control is also used for
a modulating outdoor air damper actuator for Reverse Acting Building
Pressure Control. Select NO if Modulating Building Pressure Control
is not needed when using a Constant Volume Exhaust Fan for On/Off
Control. Default is NO.

Confi guration Screen #37 - Building Pressure

Reverse Acting

RNE Cnfg ID 101

Building Pressure

Rev Acting: NO

Use < Or > To Change

Select YES if Reverse Acting Building Pressure control is needed.
Reverse Acting Building Pressure Control can either be On/Off or
Modulating Control. Modulating Control is normally used for this
confi guration. On a drop in Building Pressure, below the Building
Static Pressure Setpoint, the Outdoor Air Damper will modulate open
to increase pressure. Default is NO.

Confi guration Screen #38 - Building Pressure

Output Signal

RNE Cnfg ID 101

Building Pressure

Output Signal: 0-10V
Use < Or > To Change

This Screen is used to confi gure the Building Pressure Output Signal
voltage needed for your application. Select a 0-10 VDC signal (default)
or 2-10 VDC signal as required by the device you are using to control
the pressure. Default is 0-10V.

Confi guration Screen #39 - Heat Pump Control

RNE Cnfg ID 101

Air to Air Heat Pump

Control: NO

Use < Or > To Change

Select YES if the HVAC unit is a Heat Pump. Default is NO.

Confi guration Screen #40 - Reversing Valve

Active During Heat/Cool

RNE Cnfg ID 101

Rev. Valve Active

For: Heat

Use < Or > To Change

Select Heat if your Heat Pump unit activates its Reversing Valve dur-
ing Heating operation. Select Cool if your Heat Pump unit activates its
Reversing Valve during Cooling operation. Default is Heat.