VCM-X CONFIGURATION

33

Confi guration Screen #54 - Micro Channel

Condensers

VCM-X Cnfg ID 59

Micro Channel

Condensers: NO

Select YES if your HVAC unit is using Micro Channel Condensers.
Default is NO.

Confi guration Screen #55 - PREHEAT-X

Controller Installed

VCBX Cnfg ID 101

Preheat-X Module

Installed: NO

Use < Or > To Change

If you have a PREHEAT-X Controller installed, this confi guration option
should be confi gured as YES. Default is NO.

Confi guration Screens #56-59 - Cooling &

Heating Stage Delays

VCM-X Cnfg ID 59

Cooling Stage Delays
Staging Up...: 3 Min
Staging Down : 1 Min

VCM-X Cnfg ID 59

Cooling Stage Delays

Min Run Time: 5 Min
Min Off Time: 3 Min

VCM-X Cnfg ID 59

Heating Stage Delays
Staging Up...: 3 Min
Staging Down : 1 Min

VCM-X Cnfg ID 59

Heating Stage Delays

Min Run Time: 2 Min
Min Off Time: 1 Min

Both the Heating Stages and the DX Cooling Stages utilize Staging Up
and Down Delay Periods between stages and Minimum Run Times
and Off Times.

Both modes have their own set of Staging and Run Delay Times. The
Heating Timer Screens look exactly the same as the Cooling Timer
Screens except they reference the Heating settings instead of the Cool-
ing settings.

See the Sequence of Operation Manual for information on how these
Delays and Run Times are used.

Description

Minimum

Default

Maximum

Cooling Stage Up

3 Min

3 Min

15 Min

Cooling Stage Down

1 Min

1 Min

15 Min

Cooling Min Run Time

5 Min

5 Min

15 Min

Cooling Min Off Time

3 Min

3 Min

15 Min

Heating Stage Up

3 Min

3 Min

15 Min

Heating Stage Down

1 Min

1 Min

15 Min

Heating Min Run Time

2 Min

2 Min

15 Min

Heating Min Off Time

1 Min

1 Min

15 Min

Confi guration Screens #60-79 - Relay

Confi guration Screens

VCM-X Cnfg ID 59

Relay Configurations

Rly xx: Not Used

Use < Or > To Change

Relay #1 is not confi gurable as it is reserved for the Supply Air Fan.
Relays #2-#21 are confi gurable for the following options:

Not

Used

Pre-Heater

Heat Stage

Alarm

Cool Stage

Override

Warmup Mode

Occupied

Rev Valve

OA Damper

HGR

Heat Wheel

Exhaust Fan

Emerg. Heat

Relays #2 through #21 can be individually confi gured. By using the 4
relay outputs available on the VCM-X Controller, the 4 relays on the
VCM-X Expansion Module, and the 12 relays on the 12 Relay Expan-
sion Module, you have the ability to confi gure up to a combined total
of 20 Heating Stages, Cooling Stages, and the rest of the options listed
above. Only the Heating and Cooling relays can be confi gured with
multiple outputs. If any other option is selected more than once, it will
simply activate redundant relays, but no multiple staging will occur.

Default is “Not Used.”

VCM-X Confi guration Screens