Vcm-x / rne setpoints, Vcm-x / rne setpoint screens, Vcm-x / rne operator interface sd – Orion System VCM-X/RNE Controller User Manual

Page 51

Advertising
background image

VCM-X / RNE Operator Interface SD

VCM-X / RNE SETPOINTS

51

Setpoint Screen #24 - Building Pressure

VCM-X / RNE Spts

Building Pressure

Setpoint....: 0.10”
Deadband....: 0.02”

Direct Acting Control

If an Exhaust Fan Relay is confi gured, when the Building Static Pres-
sure rises above the Building Pressure Setpoint plus the Deadband, the
Exhaust Fan Relay will activate. It will remain on until the Building
Pressure falls below the Building Pressure Setpoint minus the Deadband.
If Modulating Building Pressure is confi gured, when the Building Static
Pressure rises above the Building Pressure Setpoint plus the Deadband,
the Building Pressure Output Signal will increase until the Building Static
Pressure falls within the Deadband. If the Building Static Pressure falls
below the Building Pressure Setpoint minus the Deadband, the Building
Pressure Output Signal will decrease until the Building Static Pressure
rises within the Deadband. The Building Pressure Output Signal is con-
fi gurable for 0-10 or 2-10 VDC. For more detailed operation information,
see the VCM-X Controller Technical Guide, VCM-X Modular E-BUS
Controller Technical Guide,
or RNE Controller Technical Guide for the
complete Building Pressure Control Sequence of Operation.

Reverse Acting Control

The Building Pressure Output Signal remains a Direct Acting 0-10 or
2-10 VDC signal, but the logic is reversed. On a drop in Building Static
Pressure below the Building Pressure Setpoint minus the Deadband, the
Building Pressure Output Signal will increase.

Description

Min.

Default

Max.

Building Pressure Spt

-0.20″ WG

0.10″ WG

0.20″ WG

Building Pressure

Deadband

0.01″ WG

0.02″ WG

0.10″ WG

Setpoint Screen #25 - RAB Damper Factor

VCM-X / RNE Spts

Return Air Bypass

Damper Factor

Setpoint..: 40%

This setpoint is used when your HVAC unit is confi gured for Return
Air Bypass Damper control. The Return Air Bypass Damper Factor
Setpoint is a percentage value that is used to calculate the Return Air
Damper position in relation to the Return Air Bypass Damper position.
This provides a method for adjusting the airfl ow through the Return
Air Bypass Damper.

Increasing this percentage increases the airfl ow through the Return Air
Bypass Damper by causing the Return Air Damper to move further
towards its closed position in relation to the Return Air Bypass Damper
moving towards its open position.

Decreasing this percentage decreases the airfl ow through the Return
Air Bypass Damper by causing the Return Air Damper to move further
towards its open position in relation to the Return Air Bypass Damper
moving towards its closed position.

Description

Minimum

Default

Maximum

Return Air Bypass

Damper Factor

0%

40%

100%

Setpoint Screen #26 - Supply Fan Starting

Delay Timer

VCM-X / RNE Spts

Fan Starting Delay

Timer...: 255 s

This is the Supply Fan Starting Delay Timer initiated whenever the
Unit Controller initiates Supply Fan operation. This is useful when you
are using multiple HVAC units and want to be sure that all the units do
not start at exactly the same time when the Occupied schedule occurs.
Each Unit Controller should be set with staggered Fan Starting Delay
Timer Setpoint values. When the 255 Second default setpoint is used,
it multiplies each Unit Controller’s address by 5 and uses this value in
seconds as the Fan Starting Delay Time. This provides a staggered start
for each Unit Controller on the system without having to individually
set each Unit Controller for its own time delay. For an MUA unit, this
should be set to a minimum of 60 seconds to let the OA Damper open.

Description

Minimum

Default

Maximum

Fan Start Delay Timer

0 Sec

255 Sec

255 Sec

Setpoint Screen #27 - Mechanical Heat/Cool

Failure Time Period

VCM-X / RNE Spts

Mechanical Heat/Cool

Failures Occur After
No Change In 15 Min

When Heating or Cooling Mode is initiated and staging is activated, if the
Supply Air Temperature does not rise or fall 5°F within the Mechanical
Heat/Cool Failures Occur After No Change For Setpoint time period,
a Mechanical Heating or Cooling failure alarm will be generated. The
Alarm is for Status Reporting only. The HVAC unit will continue to run.

Description

Minimum

Default

Maximum

Mechanical Heat/Cool

Failures Occur After

No Change For

0 Min

15 Min

255 Min

VCM-X / RNE Setpoint Screens

Advertising