Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 58 – Orion System VCM-X/RNE Controller User Manual

Page 58

Advertising
background image

VCM-X / RNE STATUS

VCM-X / RNE Operator Interface SD

58

VCM-X / RNE Status Screens

Status Screen 7 / RNE - Leaving Water

Temperature 2

RNE v1.00

Leaving Water 2

Temp A: 0.0ºF
Temp B: 0.0ºF

Line 2

Leaving Water Temperature 2

If using the RNE Controller and a second Water Source

Heat Pump Module has been installed and confi gured, this

screen will display Water Temperatures. If not, this screen

will

display

0°F.

Line 3

Leaving Water Temperature A

This line will display the Leaving Water Temperature of

the

fi rst Leaving Water Temperature Sensor on a Water

Source Heat Pump Module. If using (2) Water Source Heat

Pump Modules, this will be the fi rst sensor on the Module

with

address

2.

Line 4

Leaving Water Temperature B

This line will display the Leaving Water Temperature of

the second Leaving Water Temperature Sensor on a Water

Source Heat Pump Module. If using (2) Water Source Heat

Pump Modules, this will be the second sensor on the

Module with address 2.

Status Screen 8 - Coil Temp & Setpoint

VCM-X / RNE v1.00

Coil Tmp...: XX.XºF
Coil Tmp Spt: XX.XºF

Line 2 Coil Temperature or Lowest Coil

If a Suction Pressure Transducer has been installed and

confi gured on the unit, the calculated Evaporator Coil

Temperature will appear on this line. If not, this line will

display

0°F.

If this unit has multiple digital scroll compressors and has a

Full Digital Module or Dual Digital Module installed, this

line will display Lowest Coil and will display the lowest of

the multiple suction temperatures. The coil temperatures of

all the coils will be displayed on Status Screens 19 & 20.

Line 3 Coil Temperature Setpoint

During

dehumidifi cation, the Coil Suction Temperature

Setpoint is automatically reset based on the current space

humidity conditions. This is the current calculated Coil

Temperature Setpoint based on that reset.

Status Screen 9 - Outdoor Air Temperature &

Outdoor Air Relative Humidity

VCM-X / RNE v1.00

Outdoor Tmp: XX.XºF
Outdoor RH.: XX.X%

Line 2 Current Outdoor Air Temperature

If an Outdoor Air Temperature Sensor has been installed

and

confi gured on the unit or if an Outdoor Air Broadcast

has

been

confi gured on another Unit Controller on the

system, the Outdoor Air Temperature will appear on

this line. If not, this line will display a temperature that is

half way between the Cooling and Heating Lockout

Setpoints.

Line 3 Current Outdoor Air Relative Humidity

If an Outdoor Humidity Sensor has been installed and

confi gured on the Unit Controller, the Outdoor Air

Relative Humidity Percentage will appear on this line. If

not, this line will display 0%.

Status Screen 10 - OA Dewpoint & Dewpoint

Temp

VCM-X / RNE v1.00

OA Dewpoint.: XX.XºF
Dewpoint Spt: XX.XºF

Line 2 Current Calculated Outdoor Air Dewpoint
Temperature

If both an Outdoor Humidity Sensor and an Outdoor Air

Temperature Sensor have been installed and confi gured on

the unit, the calculated Outdoor Air Dewpoint Temperature

will appear on this line. If not, this screen displays 0°F.

Line 3 Current Outdoor Air Dewpoint Setpoint

The user adjustable Outdoor Air Dewpoint Temperature

Setpoint will appear on this line.