Rne configuration, Rne confi guration screens – Orion System VCM-X/RNE Controller User Manual

Page 37

Advertising
background image

VCM-X / RNE Operator Interface SD

RNE CONFIGURATION

37

RNE Confi guration Screens

Confi guration Screen #9 - Outdoor Humidity

Sensor

RNE Cnfg ID 101

Outdoor Humidity

Sensor: NO

Use < Or > To Change

Select YES if the HVAC unit is equipped with an Outdoor Air Humidity
Sensor. Default is NO.

Confi guration Screen #10 - Indoor Humidity

Sensor

RNE Cnfg ID 101

Indoor Humidity

Sensor: NO

Use < Or > To Change

Select YES if the HVAC unit is equipped with an Indoor Air Humidity
Sensor. Default is NO.

Confi guration Screen #11 - Heat During

Dehumidify

RNE Cnfg ID 101

Heat During

Dehumidify: NO

Use < Or > To Change

Select YES if your application needs to use unit heat during Dehumidi-
fi cation to supplement Reheat. If Reheat is not available, this selection
will allow unit heat to operate in place of Reheat. Default is NO.

Confi guration Screen #12 - Economizer

Control

RNE Cnfg ID 101

Economizer

Control: NO

Use < Or > To Change

Select YES if the RNE is controlling the Economizer. Default is NO.

Confi guration Screen #13 - Title 24

Economizer

RNE Cnfg ID 101

Title 24

Economizer: NO

Use < Or > To Change

If this unit has Title 24 Economizer operation, this option should be
confi gured as YES. Default is NO.

Confi guration Screen #14 - Proof of Flow Input

RNE Cnfg ID 101

Proof Of Flow

Input: NO

Use < Or > To Change

Select YES if the unit is equipped with a Proof of Flow Switch and
it is connected to the RNE. If selected as YES and the Proof of Flow
Switch is open, only the Supply Fan Relay will be active. If any other
relays such as Heating Stages or Cooling Stages are active, they will be
deactivated when the Proof of Flow Switch input is lost. Default is NO.

Confi guration Screen #15 - Modulating Heating

RNE Cnfg ID 101

Mod Heating: NO

Use < Or > To Change

Select YES if the HVAC unit is controlling Modulating Heating. If
your HVAC is using a Modulating Hot Water Valve, Modulating Steam
Valve, or a SCR Controlled Electric Heater, you must select YES for
Modulating Heating. This confi guration does not apply to MODGAS
using the MODGAS II Controller
. Default is NO.

Confi guration Screen #16 - Modulating

Heating Output Signal

RNE Cnfg ID 101

Mod Heating

Output Signal.: 0-10V

Use < Or > To Change

Select 0-10 VDC or 2-10 VDC as the signal for a Modulating Heat Source
such as a Hot Water Valve or SCR Electric Heater. Default is 0-10 VDC.

Confi guration Screen #17 - Modulating

Heating Reverse Acting

RNE Cnfg ID 101

Mod Heating

Rev Acting: NO

Use < Or > To Change

Select YES if the Modulating Heat Source requires 0 VDC to open and
10 VDC to close. Default is NO.