Vcm-x / rne setpoints, Vcm-x / rne setpoint screens, Vcm-x / rne operator interface sd 48 – Orion System VCM-X/RNE Controller User Manual

Page 48

Advertising
background image

VCM-X / RNE SETPOINTS

VCM-X / RNE Operator Interface SD

48

Setpoint Screen #9 - Outdoor Air Lockouts

VCM-X / RNE Spts

Outdoor Air Lockouts

Cooling......: 50ºF
Heating......: 70ºF

The Unit Controller will Lockout Mechanical Heating or Cooling when
the Outdoor Air (OA) Temperature is above or below these Setpoints.

On Air to Air Heat Pump units, Compressor Cooling and Heating can
only operate if the OA Temperature is above the Outdoor Air Cooling
Lockouts. If using the VCM-X WSHP (Water Source Heat Pump) Con-
troller, the OA Cooling Lockout is ignored. Since Emergency Heat can
only be used below the Compressor Lockouts, Emergency Heat is there-
fore not available on WSHP units using the VCM-X WSHP Controller.

Description

Minimum

Default

Maximum

OA Lockouts Cooling

0ºF

50ºF

100ºF

OA Lockouts Heating

50ºF

70ºF

150ºF

Setpoint Screen #10 - Cutoff Temperature

VCM-X / RNE Spts

Cutoff Temperatures

Lo SAT.......: 40ºF
Hi SAT.......: 170ºF

The Unit Controller will temporarily disable Heating or Cooling if while
in Heating or Cooling Mode the Supply Air Temperature rises above
the High SAT Cutoff Temperature Setpoint or falls below the Low SAT
Cutoff Temperature Setpoint. See the VCM-X Controller Technical
Guide
, VCM-X Modular E-BUS Controller Technical Guide, or RNE
Controller Technical Guide
for detailed information on the Low and
High Supply Air Temperature Cutoff sequence of operation.

Description

Minimum

Default

Maximum

Lo SAT Cutoff

0ºF

40ºF

250ºF

Hi SAT Cutoff

0ºF

170ºF

250ºF

Setpoint Screen #11 - Minimum Supply Fan

VFD Speed For Heating

VCM-X / RNE Spts

Minimum Supply

Fan VFD Speed

For Heating..: 30%

If the Supply Fan VFD Signal falls below the Minimum Supply Fan
VFD Speed For Heating Setpoint, Heating will be disabled.

VCM-X / RNE Setpoint Screens

Description

Minimum

Default

Maximum

Min Supply Fan VFD

Speed For Heating

0%

30%

100%

Setpoint Screen #12 - Morning Warm Up Temp

VCM-X / RNE Spts

Morning WarmUp

Target Temp: 72º F

Max Length.: 60 Min

When the Unit Controller is confi gured for VAV operation and the con-
troller enters the Occupied Mode, the controller looks at the Return Air
Temperature to determine if the unit should initiate Morning Warm-up
Mode. If the Return Air Temperature is below the Morning Warm-up
Target Temperature and the Max Length is greater than “0,” the control-
ler will initiate Heating. This is considered Morning Warm-up and will
run until the Return Air Temperature rises above the Morning Warm-up
Target Temperature or until the Max Length Setpoint time expires.

Description

Minimum

Default

Maximum

Morning Warm Up

Target Temp

50ºF

72ºF

90ºF

Morning Warm Up

Max Length

0 Min

60 Min

240 Min

Setpoint Screen #13 - Dehumidifi cation Indoor

RH & OA Dewpoint

VCM-X / RNE Spts

Dehumidification Spt

Indoor RH....: 50%

OA Dewpoint..: 55ºF

On VAV or CAV confi gured units that are not using 100% Outdoor Air,
when the Indoor Relative Humidity percentage rises above the Indoor
RH Setpoint, the unit will start operating in Dehumidifi cation Mode.

If an Indoor Humidity Sensor is installed, the unit will reset the Coil
Suction Temperature Setpoint as needed to maintain this Indoor RH
Setpoint. This includes VAV, CAV and MUA applications.

On MUA confi gured units that are using 100% Outdoor Air, when the
Outdoor Air Dewpoint Temperature rises above the OA Dewpoint Set-
point, the unit will start operating in Dehumidifi cation Mode.

Description

Minimum

Default

Maximum

Dehumidifi cation Setpoint

Indoor RH

1%

50%

100%

Dehumidifi cation Setpoint

OA Dewpoint

35ºF

55ºF

80ºF

Advertising