VAV/ZONE CONTROLLER PROGRAMMING

VCM-X / RNE Operator Interface SD

71

Setpoint Screen #8 - Damper Airfl ow Night Min

and Fan On Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Night Min.: XXX %
Fan On Min.:

XXX %

The Night Min is the position the damper will move to when the sys-
tem is in Override Mode and this particular damper is not part of the
override group. This Night Min position only affects non-fan powered
boxes. The Fan On Min is the minimum damper or airfl ow setting used
to activate the parallel fan if installed. Pressure Independent = CFM.
Pressure Dependent = %.

Description

Minimum

Default

Maximum

Night Min

0% or

0 CFM

0% or

0 CFM

100% or

9999 CFM

Fan On Min

0% or

0 CFM

25% or

250 CFM

100% or

9999 CFM

Setpoint Screen #9 - Damper Airfl ow Reheat Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Reheat Min.: XXX %

The Reheat Min is the damper or airfl ow setting used during the Space
Reheat Mode of operation.

Description

Minimum

Default

Maximum

Reheat Min

0% or

0 CFM

0% or

0 CFM

100% or

30000 CFM

Setpoint Screen #10 - Damper Airfl ow Fixed

Position

XX Box Spts IDXXXX

Damper/Airflow Spt

Fixed Pos: XXX %

Many times while troubleshooting a system, it is useful to have the zone
damper set to a specifi c damper position or airfl ow setting. This setpoint
can be used to determine where the damper/airfl ow will remain when
the VAV/Zone Controller receives a Force to Fixed Position command.

Description

Minimum

Default

Maximum

Fixed Pos

0% or

0 CFM

0% or

0 CFM

100% or

9999 CFM

Setpoint Screen #11 - SAT HVAC Mode

Deadband

XX Box Spts IDXXXX

SAT HVAC Mode

Deadband.: XXºF

If the supply air temperature is above the space temperature by this
amount, the VAV/Zone Controller enters the Supply Air Heating Mode.
It will remain in the Supply Air Heating Mode until the supply air drops
to 2ºF above the space temperature. At that point the unit enters the
Supply Air Vent Mode and remains there until the supply air drops this
deadband below the space temperature. At that point the VAV/Zone
Controller enters the Supply Air Cooling Mode and will remain there
until the supply air temperature rises to 2ºF below the space temperature.

Description

Minimum

Default

Maximum

SAT HVAC Mode

Deadband

0ºF

10ºF

20ºF

Setpoint Screen #12 - Zone Alarm Offsets

XX Box Spts IDXXXX

Zone Alarm Offsets

Hi Zone......: XXºF

Lo Zone......: XXºF

The VAV/Zone Controller can be setup to generate an alarm anytime the
box goes into the Occupied Mode and the Zone Temperature exceeds
the user-defi ned alarm limits for a user-defi ned period of time. A High
Temperature Alarm Setpoint is created by adding the Hi Zone Alarm
offset to the current Cooling Setpoint. The Low Temperature Alarm
Setpoint is created by adding the Lo Zone Alarm offset to the current
Heating Setpoint. If the zone temperature exceeds either of these limits
for a period defi ned by the Alarm Delay setpoint, the controller can gen-
erate an alarm callout if all the optional hardware components required
for this to occur are installed.

Description

Minimum

Default

Maximum

Hi Zone Alarm

+1ºF

+30ºF

+50ºF

Lo Zone Alarm

-1ºF

-30ºF

-50ºF

VAV/Zone Setpoint Screens