Vcm-x configuration, Vcm-x confi guration screens, Vcm-x / rne operator interface sd 30 – Orion System VCM-X/RNE Controller User Manual

Page 30

Advertising
background image

Zone

Zone

VCM-X CONFIGURATION

VCM-X / RNE Operator Interface SD

30

VCM-X Confi guration Screens

Confi guration Screen #32 - Monitor Supply Air

CFM

VCM-X Cnfg ID 59

Monitor Supply

Air CFM: NO

Use < Or > To Change

Select YES if you have an airfl ow monitoring station measuring the CFM
of the supply airfl ow stream of this unit. Default is NO.

Confi guration Screen #33 - Supply Duct/

Damper Size

VCM-X Cnfg ID 59

Supply Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the controller to properly calculate the supply air CFM, you need
to enter the area in square feet of the supply air duct/damper. When
measuring the supply duct damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.

Confi guration Screen #34 - CO

2

Sensor

Output Signal

VCM-X Cnfg ID 59

CO2 Sensor

Output Signal: None

Use < Or > To Change

The VCM-X needs to know what type of CO

2

sensor signal output is

being provided. Select either 0-10 VDC (standard sensor used) or 4-20
mA as the CO

2

sensor signal. Select None if no CO

2

sensor is used.

Default is None.

Confi guration Screen #35 - CO

2

Sensor

Maximum Scale

VCM-X Cnfg ID 59

CO2 Sensor Maximum

Scale: 2000 PPM

Enter 0 If No Sensor

The VCM-X needs to know the CO

2

Sensor scaling for proper reading

of the CO

2

Sensor output. The Standard CO

2

Sensor should be scaled to

2000 PPM. Select None if no CO

2

sensor is used. Default is 2000 PPM.

Confi guration Screen #36 - Building Pressure

Modulating Control

VCM-X Cnfg ID 59

Building Pressure

Mod Control: NO

Use < Or > To Change

Select YES if Modulating Building Pressure Control is needed. Modu-
lating Building Pressure Control is used for a VFD Exhaust Fan or a
Modulating Exhaust Fan Damper Actuator for Direct Acting Building
Pressure Control. Modulating Building Pressure Control is also used for
a modulating outdoor air damper actuator for Reverse Acting Building
Pressure Control. Select NO if Modulating Building Pressure Control
is not needed when using a Constant Volume Exhaust Fan for On/Off
Control. Default is NO.

Confi guration Screen #37 - Building Pressure

Reverse Acting

VCM-X Cnfg ID 59

Building Pressure

Rev Acting: NO

Use < Or > To Change

Select YES if Reverse Acting Building Pressure control is needed.
Reverse Acting Building Pressure Control can either be On/Off or
Modulating Control. Modulating Control is normally used for this
confi guration. On a drop in Building Pressure, below the Building
Static Pressure Setpoint, the Outdoor Air Damper will modulate open
to increase pressure. Default is NO.

Confi guration Screen #38 - Building Pressure

Output Signal

VCM-X Cnfg ID 59

Building Pressure

Output Signal: 0-10V
Use < Or > To Change

This Screen is used to confi gure the Building Pressure Output Signal
voltage needed for your application. Select either a 0-10 VDC signal
(default) or a 2-10 VDC signal as required by the device you are using
to control the pressure. Default is 0-10 VDC.

Confi guration Screen #39 - Heat Pump Control

VCM-X Cnfg ID 59

Heat Pump

Control: NO

Use < Or > To Change

Select YES if the HVAC unit is a Heat Pump. Default is NO.