Rne configuration, Rne confi guration screens – Orion System VCM-X/RNE Controller User Manual

Page 39

Advertising
background image

VCM-X / RNE Operator Interface SD

RNE CONFIGURATION

39

RNE Confi guration Screens

Confi guration Screen #26 - Type of Airfl ow

Station

RNE Cnfg ID 101

Airflow Station:

Paragon

Use < Or > To Change

Select the type of Airfl ow Monitoring Station you are using, if any.
Selections are Paragon or Ebtron. Default is Paragon.

Confi guration Screen #27 - Monitor Outdoor

Air CFM

RNE Cnfg ID 101
Monitor Outdoor

Air CFM: NO

Use < Or > To Change

Select YES if you have an Airfl ow Monitoring station measuring the
CFM of the Outdoor airfl ow stream of this unit. Default is NO.

Confi guration Screen #28 - Control Outdoor

Air CFM

RNE Cnfg ID 101

Control Outdoor

Air CFM: NO

Use < Or > To Change

Select YES if you want to control the Outdoor Air Damper to a CFM
setpoint. Default is NO.

Confi guration Screen #29 - Outdoor Duct/

Damper Size

RNE Cnfg ID 101

Outdoor Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the Controller to properly calculate the outside air CFM you need
to enter the inside area (sq. ft.) of the outdoor air duct/damper. When
measuring the outdoor air damper area, be sure to measure the inside

dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.

Confi guration Screen #30 - Monitor Return Air

CFM

RNE Cnfg ID 101

Monitor Return

Air CFM: NO

Use < Or > To Change

Select YES if you have an airfl ow monitoring station measuring the CFM
of the return airfl ow stream of this unit. Default is NO.

Confi guration Screen #31 - Return Duct/

Damper Size

RNE Cnfg ID 101

Return Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the Controller to properly calculate the return air CFM, you need to
enter the area in square feet of the return air duct/damper. When measur-
ing the return air damper area, be sure to measure the inside dimensions
of the damper. The more accurate the measurements, the more accurate
the CFM reading will be. This value needs to be accurate to 2 decimal
places. Default is 0.00.

Confi guration Screen #32 - Monitor Supply Air

CFM

RNE Cnfg ID 101

Monitor Supply

Air CFM: NO

Use < Or > To Change

Select YES if you have an airfl ow monitoring station measuring the CFM
of the supply airfl ow stream of this unit. Default is NO.

Confi guration Screen #33 - Supply Duct/

Damper Size

RNE Cnfg ID 101

Supply Duct/Damper

Size: 0.00

[Area in sq. ft.]

For the Controller to properly calculate the supply air CFM, you need
to enter the area in square feet of the supply air duct/damper. When
measuring the supply duct damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.

Advertising