Vcm-x / rne setpoints, Vcm-x / rne setpoint screens, Vcm-x / rne operator interface sd 54 – Orion System VCM-X/RNE Controller User Manual

Page 54

Advertising
background image

VCM-X / RNE SETPOINTS

VCM-X / RNE Operator Interface SD

54

Setpoint Screen #39 - PREHEAT-X Cooling

Mode and Heating Mode Setpoints

VCM-X / RNE Spts

Preheat-X Spts

Cooling Mode: 40.0ºF

Heating Mode: 60.0ºF

If using the Preheat-X Controller with the VCB-X, this screen allows
you to set the Preheat setpoint you want to control to during the Cooling
and the Heating Modes.

Description

Minimum

Default

Maximum

Preheat-X Cooling Mode
Setpoint

35.0ºF

(1.66

º

C)

40.0ºF

(4.5

º

C)

90.0ºF

(32.2

º

C)

Preheat-X Heating Mode
Setpoint

35.0ºF

(1.66

º

C)

60.0ºF

(15.5

º

C)

90.0ºF

(32.2

º

C)

Setpoint Screen #40 - PREHEAT-X Venting

Mode Setpoint

VCM-X / RNE Spts

Preheat-X Spts

Venting Mode:

50.0ºF

If using the Preheat-X Controller with the VCB-X, this screen allows you
to set the Preheat setpoint you want to control to during the Vent Mode.

Description

Minimum

Default

Maximum

Preheat-X Venting Mode
Setpoint

35.0ºF

(1.66

º

C)

50.0ºF

(10.0

º

C)

90.0ºF

(32.2

º

C)

Setpoint Screen #41 - Sensor Calibration for

SPC & SAT

VCM-X / RNE Spts

Sensor Calibration

SPC: XX.Xº 0.00º
SAT: XX.Xº 0.00º

If the Space or Supply Air Temperature Sensors are reading incorrectly,
you can use this option to enter an offset temperature to adjust the Sen-
sor’s Temperature. Enter a positive Sensor Calibration value to raise the
Space Temperature and/or Supply Air Temperature Sensor reading and
a negative value to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration SPC

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration SAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #42 - Sensor Calibration for

RAT & OAT

VCM-X / RNE Spts

Sensor Calibration

RAT: XX.Xº 0.00º
OAT: XX.Xº 0.00º

If the Return Air or Outdoor Air Temperature Sensors are reading incor-
rectly, you can use this option to enter an offset temperature to adjust
the Sensor’s Temperature. Enter a positive Sensor Calibration value to
raise the Return Air Temperature and/or Outdoor Air Temperature Sensor
reading and a negative value to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration RAT

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration OAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #43 - Sensor Calibration for

COIL

VCM-X / RNE Spts

Sensor Calibration

COIL: XX.Xº 0.00º

If the Coil Temperature reading is too high, enter a negative calibration
offset to decrease the reading. If it is too low, enter a positive value to
increase the reading.

Description

Minimum

Default

Maximum

Sensor Calibration COIL

-30.0ºF

0.0ºF

+30.0ºF

VCM-X / RNE Setpoint Screens

Advertising