Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 64 – Orion System VCM-X/RNE Controller User Manual

Page 64

Advertising
background image

VCM-X / RNE STATUS

VCM-X / RNE Operator Interface SD

64

VCM-X / RNE Status Screens

Status Screen 28 - PREHEAT-X Controller

Current Leaving Air and Entering Air

Temperature

VCM-X / RNE v1.00

Preheat-X Temps

Leaving Air: XX.XX
Entring Air: XX.XX

Line 3 Current PREHEAT-X Leaving Air Temperature

If a Leaving Air Temperature Sensor(s) has been installed

and

confi gured on the PREHEAT-X, this screen will display

the current Pre-Heat Leaving Air Temperature. If these

conditions do not exist, it will display 0°F.

Line 4 Current PREHEAT-X Entering Air Temperature

If an Entering Air Temperature Sensor has been installed

and

confi gured on the PREHEAT-X, this screen will display

the current Pre-Heat Entering Air Temperature. If these

conditions do not exist, it will display 0°F.

Status Screen 29 - PREHEAT-X Controller

Modulating Position and Active Stages

VCM-X / RNE v1.00

Preheat-X Status

Mod Pos......: XXX%
Active Stages: X

Line 3 Current PREHEAT-X Modulating Position

If you do have a PREHEAT-X Controller connected to the

VCB-X Controller and are using Modulating Heat, this is

the current modulating position of the gas valve

.

Line 4 Current PREHEAT-X Active Stages

If you have a PREHEAT-X Controller connected to the

VCB-X Controller, this is the number of Active Stages that

have

been

confi gured in the PREHEAT-X Controller’s

# of Heat Stages Confi guration Screen.

Status Screen 30 - Return Air Damper Signal

& Bypass Damper Signal

VCM-X / RNE v1.00

Return Dmp..: XXX%
Bypass Dmp..: XXX%

[Optional Outputs]

Line 2 Current Return Air Damper Signal

Indicates the current Output Signal percentage being sent to

the Return Air Damper Actuator. If you haven’t confi gured

a Return Air Bypass Damper, [No Return Dmp Confg] will

be displayed instead.

Line 3 Current Return Air Bypass Damper Signal

Indicates the current Output Signal percentage being sent to

the Return Air Bypass Damper Actuator. If you haven’t

confi gured a Return Air Bypass Damper, [No Bypass Dmp

Confg] will be displayed instead.

Line 4 Indicates That These Are Optional Outputs

This output may or may not have live data to display.

Status Screens 31-51 - Supply Fan Relay

VCM-X / RNE v1.00

Fan Relay: OFF

Cool Stage: OFF
Heat Stage: OFF

Line 2 Current Supply Fan Relay Status

The letters FRC will appear before the colon if this Relay is

in a Force Mode. On screens 31 to 51, this line will indicate

the relays use and the ON/OFF condition for that relay.

Possible options are as follows:

Not

Used

Pre-Heater

Heat

Stage Alarm

Relay

Cool

Stage

Override

Warmup

Mode

Occupied

Rev

Valve Economizer

(OA

Damper)

Gas Re-Heat ( HGR Relay)

Heat Wheel

Exhaust

Fan

Emergency

Heat

Line 3 Current relay status and description of what it is

confi gured for

The letters FRC will indicate the relay is forced to its

current

condition.

Line 4 Current relay status and description of what it is

confi gured for

The letters FRC will indicate the relay is forced to its

current

condition.