VCM-X / RNE Operator Interface SD

VCM-X / RNE SETPOINTS

49

based on the highest head pressure reading of up to 4 Head Pressure
Sensors. This screen only applies if using the VCM-X E-BUS Control-
ler, or RNE Controller.

See the One Condenser Head Pressure Module Technical Guide, the
Two Condenser Head Pressure Module Technical Guide, or the RNE
Controller Technical Guide
for detailed information.

Description

Minimum

Default

Maximum

Reheat Head Pressure

Setpoint

200 PSI

400 PSI

400 PSI

Setpoint Screen #17 - Economizer OAT/WB

Enable

VCM-X / RNE Spts

Economizer Setpoints

OAT/WB Enable: 55ºF

If an Outdoor Air Humidity Sensor is not connected to the Unit Con-
troller and the Outdoor Air Temperature falls below this Setpoint, the
Economizer can be used for Free Cooling. If an Outdoor Air Humidity
Sensor is connected to the controller, then a Wetbulb Temperature will
be calculated and used instead of the Outdoor Air Drybulb Temperature
to determine when Free Cooling can be used.

Description

Minimum

Default

Maximum

Economizer Setpoints

OAT/WB Enable

0ºF

55ºF

80ºF

Setpoint Screen #18 - Economizer Minimum

Position & Control Rate

VCM-X / RNE Spts

Economizer Setpoints

Min Position.: 10 %

Control Rate.: 90

The Economizer (OA Damper) Min Position Setpoint is maintained
during the Occupied Mode even if the Economizer is disabled due to the
OA Temperature or Wetbulb Temperature being above the Economizer
Enable Setpoint. The Control Rate Setpoint allows you to adjust the
Economizer to modulate the OA Damper Actuator faster or slower as
desired. The Control Rate Setpoint range is 10-99. Larger numbers make
the Economizer Outdoor Air Damper Actuator modulate faster, smaller
numbers make the Outdoor Air Damper Actuator modulate slower.

Description

Minimum

Default

Maximum

Economizer Min Position

0%

10%

100%

Economizer Control Rate

10

90

99

VCM-X / RNE Setpoint Screens

Setpoint Screen #14 - Dehumidifi cation Coil

Temperature

VCM-X / RNE Spts
Dehumidification
Coil Temperature

Setpoint.....: 45ºF

During the Dehumidifi cation Mode, the Unit Controller uses the cal-
culated Coil Temperature to activate DX Cooling based on this Dehu-
midifi cation Coil Temperature Setpoint. The controller uses a Suction
Pressure Transducer to read Suction Pressure (the Saturation Vapor
Pressure of the Refrigerant) and converts this Suction Pressure reading
to a Coil Temperature value. This calculation is based on using R22 or
R410A refrigerant only and will not work with any other refrigerant.
This setpoint determines the number of compressor stages that need to
be activated to maintain the Dehumidifi cation Coil Temperature Setpoint.

Description

Minimum

Default

Maximum

Dehumidifi cation Coil
Temperature Setpoint

35ºF

45ºF

70ºF

Setpoint Screen #15 - Cooling Head Pressure

Setpoint

VCM-X / RNE Spts

Cooling

Head Pressure

Setpoint: 315PSI

If you are using the Head Pressure Module, this is the Cooling Setpoint
for control of the condenser fan speed. This is based on the highest
head pressure reading of up to 4 Head Pressure Sensors. This screen
only applies if using the VCM-X E-BUS Controller, or RNE Controller.

See the One Condenser Head Pressure Module Technical Guide, the
Two Condenser Head Pressure Module Technical Guide, or the RNE
Controller Technical Guide
for detailed information.

Description

Minimum

Default

Maximum

Cooling Head Pressure

Setpoint

200 PSI

315 PSI

400 PSI

Setpoint Screen #16 - Reheat Head Pressure

Setpoint

VCM-X / RNE Spts

Reheat

Head Pressure

Setpoint: 400PSI

If you are using the Head Pressure Module, this is the Reheat Setpoint
for control of the condenser fan speed during dehumidifi cation. This is

Advertising