15 Electrical

Specifications

15.1 Earth

Continuity


Test Current (2

Ÿ load)

±200 mA

Test Circuit Voltage

± 4V min

Test Duration

2, 5, 10, 20, 30 seconds

Pass/Fail

Limit

User

Defined

Display

Range

0.00

19.99

Ÿ

Measuring Range

0.01 – 19.99

Ÿ

Resolution

0.01

Ÿ

Accuracy

±

5%

±2

digits

15.2 Insulation

Resistance


Test Voltage Open Circuit

250V or 500V +20% / -0%

Test Voltage @ 1mA

250V or 500V min

Test Current Short Circuit <2

mA

Test

Duration 2,

5,

10,

20,

30

seconds

Pass/Fail

Limit

User

Defined

Display

Ranges

0.00

1.99M

Ÿ

2.0

19.9M

Ÿ

20 – 199M

Ÿ

Measuring

Range

0.01

40M

Ÿ

Resolution

0.01M

Ÿ, 0.00 – 1.99MŸ

0.1M

Ÿ, 2.0 – 19.9MŸ

1M

Ÿ, 20 – 199MŸ

Accuracy

± 5% ±2 digits

15.3 Substitute

Leakage


Test Voltage

40V a.c 50Hz open circuit

Test Duration

2s – 30s

Pass/Fail

Limit

User

Defined

Display

Range

0.15

19.99mA

Measuring Range

0.25 – 19.99mA

Resolution

0.01mA

Accuracy

± 5% ± 2 digits


Note: The displayed measurements can be scaled

for a supply voltage of 230 V, 244 V or 253 V
depending on configuration( i.e. 230 + 0 %,
+6% or +10%).