System power consumption, Heat dissipation, Environmental specifications – H3C Technologies H3C SecPath M9000 Series User Manual

Page 57: Table 13

Advertising
background image

49

Table 13 Fan tray power consumption

Model

Minimum fan tray power

consumption

Maximum fan tray power

consumption

M9006

12 W

240 W

M9010

13 W

329 W

M9014 (upper fan tray)

9 W

200 W

M9014 (lower fan tray)

7 W

124 W

System power consumption

The system power consumption of the gateway depends on the type and number of cards and the fan

tray power consumption.

The minimum system power consumption is the total static power consumption of all cards plus the
minimum fan tray power consumption.

The maximum system power consumption is the total dynamic power consumption of all cards plus
the maximum fan tray power consumption.

For example, for an M9006 gateway that has two MPUs NSQ1SUPB0s, one service module

NSQ1FWCEA0 , two switching fabric modules NSQ1FAB04B0s, and one fan tray, the minimum system

power consumption of the gateway is 2 x 45 + 1 x 109 + 2 x 48 + 12=307 W, and the maximum system

power consumption of the gateway is 2 × 50 + 1 × 157 + 2 × 65 + 240 = 627 W.

Heat dissipation

Heat dissipation is measured in BTU/h, and 1 W equals 3.4121BTU/h.
The heat dissipation of a gateway depends on its power consumption. To calculate heat dissipation of

the gateway, assume 90% power consumption is converted to heat, and the efficiency of the power
module is 90%. Heat dissipation/hour of the gateway is 0.9 × (total power consumption of the cards

plus power consumption of the fan tray)/0.9 × 3.4121.
For the power consumption of the cards and fan trays of the M9000 gateways, see "

Module power

consumption and system power consumption

."

Environmental specifications

Table 14 Environmental specifications

Description Operating

Non-operating

Temperature

0°C to 45°C (32°F to 113°F)

–40°C to +70°C (–40°F to +158°F)

Relative humidity

10% to 95% (non-condensing)

5% to 95% (non-condensing)