Emerson MICRO MOTION 1700 User Manual

Page 69

Advertising
background image

5.6

Wire the remote core processor to the sensor

using jacketed cable

For ATEX installations, the jacketed cable must be installed inside a user-supplied sealed
metallic conduit that provides 360° termination shielding for the enclosed cable.

CAUTION!

Sensor wiring is intrinsically safe. To keep sensor wiring intrinsically safe, keep the sensor
wiring separated from power supply wiring and output wiring.

CAUTION!

Keep cable away from devices such as transformers, motors, and power lines, which produce
large magnetic fields. Improper installation of cable, cable gland, or conduit could cause
inaccurate measurements or flow meter failure.

CAUTION!

Improperly sealed housings can expose electronics to moisture, which can cause measurement
error or flowmeter failure. Install drip legs in conduit and cable, if necessary. Inspect and
grease all gaskets and O-rings. Fully close and tighten all housing covers and conduit openings.

1.

Run the cable through the conduit. Do not install 9-wire cable and power cable in
the same conduit.

2.

To prevent conduit connectors from seizing in the threads of the conduit openings,
apply a conductive anti-galling compound to the threads, or wrap threads with PTFE
tape two to three layers deep.

Wrap the tape in the opposite direction that the male threads will turn when
inserted into the female conduit opening.

3.

Remove the junction box cover and core processor end-cap.

4.

At both the sensor and transmitter, do the following:

a. Connect a male conduit connector and waterproof seal to the conduit opening

for 9-wire.

b. Pass the cable through the conduit opening for the 9-wire cable.
c. Insert the stripped end of each wire into the corresponding terminal at the

sensor and transmitter ends, matching by color. No bare wires should remain
exposed.

Sensor and remote core processor terminal designations

Table 5-6:

Wire color Sensor terminal Remote core processor terminal Function

Black

No connection

Ground screw (see note)

Drain wires

Brown

1

1

Drive +

Red

2

2

Drive –

Mounting and sensor wiring for remote core processor with remote sensor installations

Installation Manual

65