Channel configuration, Chapter 9, 1 channel configuration – Emerson MICRO MOTION 1700 User Manual

Page 99

Advertising
background image

9

I/O wiring for Model 2700

transmitters with configurable input/

outputs

Topics covered in this chapter:

Channel configuration

mA/HART wiring

Frequency output wiring

Discrete output wiring

Discrete input wiring

9.1

Channel configuration

The six wiring terminals are divided into three pairs, and called Channels A, B, and C.
Channel A is terminals 1 and 2; Channel B is terminals 3 and 4; and Channel C is terminals 5
and 6. Variable assignments are governed by channel configuration.

Channel configuration

Table 9-1:

Channel

Terminals

Configuration options

Power

A

1, 2

mA output with HART/Bell202

Internal

B

3, 4

mA output (default)

Internal

Frequency output

Internal or external

Discrete output

Internal or external

C

5, 6

Frequency output (default)

Internal or external

Discrete output

Internal or external

Discrete input

Internal or external

Notes

For Channel A, the Bell 202 signal is superimposed on the mA output.

You must provide power to the outputs when a channel is set to external power.

When both Channel B and Channel C are configured for frequency output (dual pulse),
frequency output 2 is generated from the same signal that is sent to the first frequency
output. Frequency output 2 is electrically isolated but not independent.