Orientation, 6 orientation, M= 18v + ( r × l × 0.5a) – Emerson MICRO MOTION 1700 User Manual

Page 12

Advertising
background image

18 to 100 VDC, 6 watts typical, 11 watts maximum

Complies with low voltage directive 2006/95/EC per EN 61010-1 (IEC 61010-1) with
amendment 2, and Installation (Overvoltage) Category II, Pollution Degree 2

Note

For DC power:

Power requirements assume a single transmitter per cable.

At startup, the power source must provide a minimum of 1.5 amps of short-term current per
transmitter.

Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.5 amps.

Cable sizing formula

Figure 1-8:

M

= 18V + (R × L × 0.5A)

M: minimum supply voltage

R: cable resistance

L: cable length

Typical power cable resistance at 68 °F (20 °C)

Table 1-6:

Wire gauge

Resistance

14 AWG

0.0050 Ω/ft

16 AWG

0.0080 Ω/ft

18 AWG

0.0128 Ω/ft

20 AWG

0.0204 Ω/ft

2.5 mm

2

0.0136 Ω/m

1.5 mm

2

0.0228 Ω/m

1.0 mm

2

0.0340 Ω/m

0.75 mm

2

0.0460 Ω/m

0.50 mm

2

0.0680 Ω/m

1.6

Orientation

You can mount the transmitter in any orientation as long as the conduit openings do not
point upward.

CAUTION!

Upward-facing conduit openings risk condensation moisture entering the transmitter housing,
which could damage the transmitter.

Planning

8

Micro Motion

®

Model 1700 and 2700