Appendix B

Two-Cell Applications

Ion Exchange

Ion exchange operations can achieve especially precise control using the conductivity ratio of
two points with each bed. Ratio measurement accounts for feedwater variations when the
upstream point is measured at the cation bed inlet. With the upstream point in the bed as shown
for following stages, it can identify exhaustion before breakthrough.

Cell 2

Cell 2
Cell 1

Cell 2
Cell 1

Inlet

Cell 1

Mixed Bed

D I Water

Cation Bed

Anion Bed

a/n 23188

Reverse Osmosis

Reverse Osmosis efficiency is monitored by comparing inlet and outlet conductivity (or TDS).
Automatic calculations of Percent Rejection or Percent Passage are provided. If readout is in
resistivity, cell locations are interchanged. Temperature readout assists with normalized
performance comparisons.

R O U n it

C on ce n trate

C e ll 1

C e ll 2

F ee d

Pe rm ea te

a/n 2318 9

Percent Passage =

Cell

Cell

x

1

2

100

Typical Range is 0 to 20%

Percent Rejection =

(

)x

1

1

2

100

Cell

Cell

Typical Range is 80 to 100%