I/O Setup and System Configuration

7/99

9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual

5-21

5.9 Selecting a Computed Value to Be Displayed

Purpose

The Analyzer/Controller can calculate and display a computed value. The available values are:

RATIO: ratio between the values measured by the cells;

Cell

Cell

1

2

DIFFERENCE: difference between the values measured by the cells;

Cell

Cell

1

2

%PASSAGE: computed percent passage:

Cell

Cell

x

1

2

100

%REJECTION: computed percent rejection:

(

)x

1

1

2

100

Cell

Cell

PPMCO2: computed parts per million carbon dioxide (standard range analyzers only)

Appendix B includes examples of applications using these values.

ATTENTION

If a computed value is used, it is significant which cell is considered “Cell 1” and which is
“Cell 2”. This must be taken into account when wiring the inputs. See 6.3 for details.

Procedure

Use the procedure in Table 5-9 to specify a computed value.

Table 5-9 Procedure for Specifying a Computed Value

Step

Screen

Action

1

MENU
CONFIGURATION
CALIBRATION
MAINTENANCE
I/O SETUP

DIAGNOSTICS
| PREV | NEXT

Go to CONFIGURATION | ADVANCED FEATURES |
COMPUTED VALUE.

CONFIGURATION
CAT/RETRANSMISSION
ALARMS
DISCRETE CONTROL

ADVANCED FEATURES

DIAGNOSTICS
| PREV | NEXT

ADVANCED FEATURES
CLOCK SETUP

COMPUTED VALUE

AUTO CLEAN

DIAGNOSTICS
| PREV | NEXT