Automatic wash setup autoclean operation – Honeywell 9782 Series User Manual

Page 97

Advertising
background image

AutoClean Theory and Piping

7/99

9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual

7-3

Automatic Wash Setup

AutoClean Operation

Interval Between Rinses

(days or hours)

0.588" 0.222"

1.709"

Normal Operation

Resume Delay Time (seconds)

Rinse Duration (seconds)
Relay 1 Activated

TIME

Outputs & Alarms Held

rinse/cleaning

solution

process

sample

cell

to process

to drain

9782

S4

S1

Items outside this area
provided by user

a/n 23185

Figure 7-1 Automatic Cell Wash Setup

Select valves and fittings with appropriate pressure ratings

Make the process connections as shown in Figure 7-1. Be sure that valves and fittings (S1) have
sufficient pressure ratings to withstand pressure peaks which will occur when process flow is
blocked.

Minimize liquid volume in system

Keep pipe sizes small and couplings close to minimize the liquid volume in the system. Smaller
volumes require less time to rinse.