A strong exhaust fan will create a vacuum in the room. For an

exhaust system vent to work properly, exhaust and make-up

air must be balanced properly. For proper air balance contact

your local H.V.A.C. contractor.

All gas burners and pilots need sufficient air to operate and

large objects should not be placed in rear and bottom of this

oven, which would obstruct the airflow through the front.

INSTALLATION OF A DIRECT FLUE.

When the installation of a canopy type exhaust hood is

impossible the oven may be direct vented. Before direct

venting check your local codes on ventilation, in the absence

of local codes, refer to the National Fuel Code NFPA 54, ANSI

Z223.1 (latest revision).

If the unit is to be connected directly to a direct flue, it is

necessary that draft diverter be installed to insure proper

ventilation.

DRAFT DIVERTER

Direct venting as described above, should be positioned

on the main top and fastened with sheet metal screws

provided. All parts described above are available from the

manufacturer.

NOTE: Each oven has been factory tested and adjusted prior

to shipment. It may be necessary to further adjust the oven

as part of a proper installation. Such adjustments are the

responsibility of the installer. Adjustments are not considered

defects in material and workmanship, and they are not

covered under the original equipment warranty.

DO NOT UNDERSIZE VENT PIPE!

This can cause resistance to flow and impede good venting.

We suggest that if a horizontal run must be used it should

rise no less than 1/4" (6.25mm) for each linear foot of run, and

after a total of 180° of bends you should increase the size of

stove pipe by two (2") inches. The flue should rise 2' (60cm) to

3' (90cm) above the roof line or 2' (60cm) to 3' (90cm) above

any portion of a building within a horizontal distance of 10 (3

meters) feet.

The following diagram is only one example from the National

Fuel Gas Code Book NFPA 54, ANSI Z223.1, 7.5.3: