Service – Garland 200 User Manual

Page 30

Advertising
background image

Page 30

Part # MCOSM06 Rev 1 (11/03/08)

SERVICE

Preliminary Check

The following visual checks should be made before trouble

shooting and after installation or maintenance.

1. Check power to the appliance and S86.

2. Manual shutoff cocks in the gas line must be open.

3. Make certain all wiring connections are clean and tight.

4. First de-energize the system and wait at least one (1)

minute. This resets the module allowing a return to the

start condition.

5. Review the S86 system normal sequence of operation.

System Trouble Shooting

Start the system by setting the controller above the required

temperature. Observe the system response. Establish the type

of malfunction or deviation from the normal operation. Use

the S286 Intermittent Pilot system trouble shooting table to

check for normal system operation.

Use the table by following the instruction questions in the

box. If the conditions is true or okay (answers yes), go down

to the next box underneath. If the condition is not true of

not okay (answer no), go right to the next box alongside.

Continue checking and answering conditions in each box

encountered, until a problem and/or the repair is explained.

After any maintenance or repair, the trouble shooting

sequence should be repeated until the trouble shooting

procedure ends with a normal system operation.

Check Grounding

A common ground is required for the pilot burner, the

igniter-sensor, the GND terminal of the S86, and the main

burner. The main burner generally serves as the common

ground. If the ground it poor or erratic, safety shutdowns may

occur occasionally even though operation is normal at time

of check out. Therefore, if nuisance shutdowns have been

reported, be sure to check the grounding.

Note: If the ground circuit path is incomplete, the S86H

system control will allow one trial for ignition before going

into safety lock out.

Electric grounding connections at the pilot burner,

igniter/sensor and S86 must be clean and tight. If a lead

wire is damaged or deteriorated, use only No. 14 or 18

gauge moisture resistant thermoplastic insulated wire

with 105°C (221°F) minimum ratings as replacement.

Excessive temperature at the ceramic flame rod can also

permit electrical leak to ground. Examine the flame rod and

mounting bracket, and correct if bent out of position. Replace

igniter/sensor if insulator is cracked.

Check Spark Ignition Circuit

The electronic module and step-up transformer in the S86

provides a spark ignition at 30,000 volts (open circuit). This

circuit can be checked at the S86 module as follows:

1. Turn off the manual gas cock to prevent the flow of gas.

2. Disconnect the ignition cable at the S86 stud terminal to

isolate the circuit from the pilot burner/igniter/sensor, and

prepare a shot jumper lead using heavily insulated wire,

such as ignition cable.

3. Energize the S86 touch one of the jumper firmly to the S86

ground terminal (GND). Do not disconnect the existing

ground lead. Move the free end slowly toward the stud

terminal to establish a spark and then pull the lead wire

slowly away from the stud. Not the length of the gap at

which the arching stops.

CAUTION: Do not touch either the stripped end of the jumper

or stud terminal. This is a very high voltage circuit and

electrical shock can result. Perform the test immediately upon

energizing the system – before the S86H goes into safety lock

out and interrupts the spark circuit.

4. An arch length of 1/8" (3.2mm) or more indicates a

satisfactory voltage output. Replace the S86 if not arc

can be established or the maximum gap is less then 1/8"

(3.2mm), and the fuse and power to the S86 input terminal

was okay.

Advertising