If the main burner flame extinguishes during the run state,

the control de-energizes the main gas valve for an interpurge

of 30 seconds. After this period, another trial for ignition is

initiated. If this flameout cycle repeats for a total of 16 times

(main burner flame established, then lost), the control will:

• Enter the lockout mode if the control is a G760. The

thermostat contacts must be opened for 30 seconds and

then closed to escape the lockout condition.

• Enter the 100% shutoff mode and recycle period (5

minute recycle delay for the G765 and 60 minute recycle

delay for the G766) before beginning another trial for

ignition, starting with prepurge.

Wiring Diagram for G76x Ignniton Control

Main Burner

Ground

Spark Electrode/

Sensor Assembly

G76x Ignition Control

Limits In

Thermostat

Line Only

Thermostat

Transformer

Power

Supply

MAIN

VALVE

MAIN

VALVE

GROUND

5

LED

THS 2

M.V. 3

SENSE 4