Trouble shooting table – Garland 200 User Manual

Page 29

Advertising
background image

Part # MCOSM06 Rev 1 (11/03/08)

Page 29

NO

NO

NO

NO

NO

NO

NO

NO

START

YES

YES

YES

YES

YES

YES

YES

YES

Note: Before trouble shooting familiarize yourself with

the startup procedure.

TURN GAS SUPPLY OFF.

TURN CONTROLLER TO

CALL FOR HEAT POWER

TO MODULE

(24V NOMINAL)

SPARK ACROSS IGNITER/

SENSOR GAP

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

SPARK STOPS WHEN

PILOT IS LIT?

MAIN BURNER LIGHTS?

SYSTEM RUNS UNTIL

CALL FOR HEAT LOSS?

TROUBLE SHOOTING

ENDS

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

Check line voltage power, low voltage transformer, limit controlled and wiring.

• Check ignition cable, ground wire, ceramic insulator and gap and correct.
• Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield

cable and boot from excess temperature.

• On models with vent damper plug, make sure vent damper

had not be installed, the remove. Replace vent damper if

necessary.

• On other models, replace module

Pull ignition lead

and check spark and

module.

Spark okay?

• Check that all manual gas valves are open, supply tubing and pressure are good, and pilot burner

orifice is not blocked.

• Check electric connections between module and pilot operator on gas control.
• Check for 24 VAC across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if

not, replace module.

Note: If S5800B, H; S6810B, H goes into lockout, reset system. For S6800M, wait 6 minutes nominal

for retry or reset system

• Check continuity of ignition cable to ground wire.
• Clean flame rod.
• Check electrical connection between flame rod and module.
• Check for cracked ceramic flame rod insulator.
• Check that the pilot flame covers the road and is steady and blue.
• Adjust pilot flame.
• If problem persists, replace module.

Note: If S8600B, H; S6810B, H goes into lockout, reset system. For S6800M, wait 6 minutes, nominally

for retry or reset system.

• Check continuity of ignition cable and ground wire.
Note. If ground is poor or erratic, shutdowns may occur occasionally even though operation is

normal at the time of checkout.

• Check that the pilot flame covers flame rod and is steady and blue.
• If checks are okay, replace the module.

• Check for 24 VAC across MV-MV\PV terminals. If no voltage, replace module.
• Check electrical connections between module and gas control. If okay, replace gas control or gas

control operator.

• Check for proper controller operation
• Remove MV lead at module; if valve closes, recheck the temperature controller and wiring; if not,

replace gas control.

Repeat procedure until trouble free operation is obtained.

TROUBLE SHOOTING TABLE

Advertising